Modbus Read, Write and Override Parameters plus Exception Codes
364
UDC3500 Universal Digital Controller Product Manual
3/07
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Segment #8
PID SET
198
40C6
16582
INT
R/W
0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #9
Ramp Time
0045
069 FP
R/W
99.59
(0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #9
PID SET
199
40C7
16583
INT
R/W
0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #10
Soak Setpoint
Value
70
0046
070
FP
R/W
Within Setpoint Limits
Segment #10
Soak Time
71 0047
071 FP R/W 99.59
(0-99
Hrs:0-59 Min)
Guaranteed
Soak ##10
91
405B
16475
FP
R/W
0 to 99.9 (0 = no soak)
Segment #10
PID SET
200
40C8
16584
INT
R/W
0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #11
Ramp Time
72 0048
072 FP R/W 99.59
(0-99
Hrs:0-59 Min) or
0 to 999
(Degrees/Minute)
Segment #11
PID SET
201
40C9
16585
INT
R/W
0 = SET1
1 = SET2
2 = SET3
3 = SET4
Segment #12
Soak Setpoint
Value
73
0049
073
FP
R/W
Within Setpoint Limits
Segment #12
Soak Time
74 004A
074 FP R/W 99.59
(0-99
Hrs:0-59 Min)
Guaranteed
Soak ##12
92
405C
16476
FP
R/W
0 to 99.9 (0 = no soak)
Segment #12
PID SET
202
40CA
16586
FP
R/W
0 = SET1
1 = SET2
2 = SET3
3 = SET4
Summary of Contents for UDC3500