Modbus Read, Write and Override Parameters plus Exception Codes
3/07
UDC3500 Universal Digital Controller Product Manual
385
10.7.7 Accutune
Table 10-16 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Adaptive Tune.
Table 10-16 Set-up Group – Adaptive Tune
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Fuzzy Overshoot
Suppression
193
00C1
193
INT
R/W
0 = Disabled
1 = Enabled
Fuzzy Overshoot
Suppression Loop2
193
01C1
449
INT
R/W
0 = Disabled
1 = Enable 1
2 = Enable 2
3 = Enable 12
Accutune Enable
Loop 1
152
0098
152
INT
R/W
0 = Accutune Disabled
1 = Limit Tune
2 = SP Tune
3 = Tune + SP
4 = SP Tune + PV
Accutune Enable
Loop2
152
0198
408
Int
R/W
0 = Accutune Disabled
1 = Limit Tune
2 = SP Tune
3 = Tune + SP
4 = SP Tune + PV
Accutune Duplex
selection
225
00E1
225
INT
R/W
0 = Manual
1 = Auto
2 = Disable (blend)
Accutune Error (Read
only) Loop1
151
0097
151
INT
R/W
0 = None
1 = Output Limits
2 = PV Change
Insufficient
3 = Process
Identification Failed
4 = Accutune Aborted
5 = Running
6 = Setpoint Error
Accutune Error (Read
only) Loop2
151
0197
407
INT
R/W
0 = None
1 = Output > or < Output
Limits or Man Step=0
2 = PV Change
Insufficient
3 = Process
Identification Failed
4 = Accutune Aborted
5 = Running
6 = Setpoint Error
Tune Criteria
139
008B
139
INT
R/W
0 = Normal
1 = Fast
Summary of Contents for UDC3500
Page 16: ......