Modbus Read, Write and Override Parameters plus Exception Codes
3/07
UDC3500 Universal Digital Controller Product Manual
395
10.7.10 Logic
Table 10-19 lists all the register addresses and ranges or selections for the function
parameters in Set-up Group Logic
Table 10-19 Set-up Group – Logic
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Logic Gates
150
4096
16534
INT
R/W
0 = Disable
1 = Enable
Gate 1 Type
151
4097
16535
INT
R/W
0 = Not Used
1 = OR
2 = NOR
3 = AND
4 = NAND
5 = XOR
6 = XNOR
7 = B LT A
8 = B GT A
Gate 2 Type
155
409B
16539
INT
R/W
Same as ID 151
Gate 3 Type
159
409F
16543
INT
R/W
Same as ID 151
Gate 4 Type
163
40A3
16547
INT
R/W
Same as ID 151
Gate 5 Type
167
40A7
16551
INT
R/W
Same as ID 151
Gate 1 InputA
(OR, NOR,
AND, NAND, X
OR, X NOR)
152
4098
16536
INT
R/W
0 = Digital Input 1
1 = Digital Input 2
2 = Digital Input 3
3 = Digital Input 4
4 = Relay 1
5 = Relay 2
6 = Relay 3
7 = Relay 4
8 = Relay 5
9 = Gate Out 1
10 = Gate Out 2
11 = Gate Out 3
12 = Gate Out 4
13 = Gate Out 5
14 = FIX ON
15 = FIX OFF
16 = MA MODE
17 = LR SPL1
18 = ADAPT1
19 = MA MODE2
20 = LR SPL2
21 = ADAPT2