Modbus Read, Write and Override Parameters plus Exception Codes
404
UDC3500 Universal Digital Controller Product Manual
3/07
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
ATTENTION
Changing the Input Type will result in the loss of Field Calibration values and will restore the
Factory Calibration values.
Input 2 Transmitter
Characterization
171 00AB
171
INT R/W
0 = B TC
1 = E TC H
2 = E TC L
3 = J TC H
4 = J TC M
5 = J TC L
6 = K TC H
7 = K TC M
8 = K TC L
9 = NNM H
10 = NNM L
11 = Nicrosil H TC
12 = Nicrosil L TC
13 = Plat H
14 = Plat L
15 = R TC
16 = S TC
17 = T TC H
18 = T TC L
19 = W TC H
20 = W TC L
21 = 100 PT RTD
22 = 100 PT LO RTD
23 = 200 PT RTD
24 = 500 PT RTD
25 = 1000PT
26 = Radiamatic RH
27 = Radiamatic RI
28 = Linear
29 = Square Root
Input 2 High
Range Value
035
0023
035
FP
R/W
–999. to 9999.
Engineering Units
Input 2 Low Range
Value
036
0024
036
FP
R/W
–999 to 9999.
Engineering Units
Input 2 Ratio
037
0025
037
FP
R/W
–20.00 to 20.00
Input 2 Bias
038
0026
038
FP
R/W
–999 to 9999.
Engineering Units
Input 2 Filter
43
002B
043
FP
R/W
0 to 120 seconds
Input 2 Emissivity
44
002C
044
FP
R/W
0.01 to 1.00
Input 2 Burnout
165
00A5
165
INT
R/W
0 = None
1 = Up
2 = Down
3 = No Failsafe