Modbus Read, Write and Override Parameters plus Exception Codes
3/07
UDC3500 Universal Digital Controller Product Manual
413
Parameter
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Description
ID
Hex
Decimal
Output Deadband for
Time Duplex
18
0012
018
FP
R/W
–5 to +25.0%
Output Deadband for
TPSC
76
004C
076
FP
R/W
0.5 to 5.0%
Output Drop Off
Limit
20
0014
020
FP
R/W
–5 to 105%
Output Hysteresis
19
0013
019
FP
R/W
0.0 to 100.0% of PV
Failsafe Mode
213
00D5
213
INT
R/W
0 = Latching
1 = Non latching
Failsafe Output
Level
40
0028
040
FP
R/W
0 to 100%
TPSC Power Output
183
00B7
183
INT
R/W
0 = Last
1 = Failsafe
TPSC Failsafe
Output
184
00B8
184
INT
R/W
0 = Motor goes to closed
position (0%)
1 = Motor goes to open
position (100%)
Manual Output
113
0071
113
FP
R/W
0 to 100%
Automatic Output
114
0072
114
FP
R/W
0 to 100%
Proportional Band
Units
148
0094
148
INT
R/W
0 = Gain
1 = Proportional band
Reset Units
149
0095
149
INT
R/W
0 = Minutes
1 = RPM
Summary of Contents for UDC3500