background image

UV100E ULTRAVIOLET SYSTEMS

7

68-0262—5

16.

For air treatment systems, wait ten minutes for the 

airflow sensor to calibrate. During this time, the furnace 

fan must remain off.

NOTE: Failure to wait ten minutes for the airflow sensor to 

calibrate before powering the furnace causes the 

airflow sensor to incorrectly calibrate and the device 

to incorrectly function. If this occurs, remove power to 

the furnace or turn off the system and fan, wait ten 

minutes, and then resume normal furnace operation.

17.

Reconnect the power to the HVAC system.

18.

Choose a location on the adjacent HVAC equipment for 

the HVAC maintenance UV warning label included in the 

UV system packing box. Choose a location that a future 

installer can easily see during any future HVAC 

maintenance or repair.

19.

Adhere the HVAC maintenance UV warning label to the 

HVAC equipment (selected in step 17) such as the 

furnace, air cleaner or humidifier. See Fig. 8.

Fig. 8. HVAC maintenance UV safety label.

CHECKOUT

The installer should verify that the ultraviolet bulb(s) are 

operating 

only

 

by viewing the lamp light indicator

 

on the lamp 

handle.

 

Do not attempt to look directly into the duct to see the 

illuminated ultraviolet bulbs.

 See Fig. 9.

Fig. 9. Lamp light indicator, LED and reset button.

The installer should orient the homeowner to the unit by 

showing them the blue glow of the lamp light indicator and 

discussing how to determine when the unit is functioning 

properly without looking directly into the duct to see the 

illuminated ultraviolet lamp. The installer should also 

emphasize the hot surface and electrical shock safety 

warnings.

The installer should show the homeowner the LED on the front 

of the UV system and explain operation as follows:

 a

Bulb life means emitting adequate amount of UV-C energy to 

maintain an effective kill rate. At 0% bulb life remaining, the 

lamp continues to operate until catastrophic bulb failure (bulb 

burns out) but the kill rate becomes rapidly negligible.

Installer should also orient the homeowner to the reset button 

on the bottom of the UV system that, when pressed briefly for 

one second, can be used to command lamp on for the 

minimum run time of 40 minutes (air treatment system) or three 

hours (surface treatment system), depending on system type. 

And that when a new bulb is installed, the homeowner must 

hold the reset button for five seconds to reset the internal 

timers. Cycling power does not reset internal timers.

When using Enviracom communication bus to communicate 

with other appliances, the installer should orient the home-

owner to the Enviracom LED and three screw terminals. The 

Enviracom LED flashes when transmitting and lights solidly 

when there is a fault. 

The installer should also explain the extended-bulb life for the 

surface treatment system. For the single-lamp and dual-lamp 

air treatment systems, the installer should orient the home-

owner to the alternate method of using the UV system to 

monitor the thermostat load information to turn lamp off and on 

instead of using the air flow sensor to control lamp operation 

and that it communicates the percent remaining bulb life.

The installer should leave the Owner’s Guide with the 

homeowner and review the bulb cleaning and replacement 

procedures. A Bulb Cleaning Reminder Schedule is included in 

the Owner’s Guide to help the homeowner set up and track a 

regular cleaning schedule.

M22868

M22855

LAMP LIGHT 

INDICATOR

LED CHANGE 

INDICATOR

RESET 

BUTTON

LED Status

Indicates

Homeowner Action

Off

100 to 11% bulb life

a

 

remaining

Nothing

Flashing

10 to 1% bulb life

a

 

remaining

Purchases bulb(s)

Solid

0% bulb life

a

 remaining Replaces bulb(s)

Summary of Contents for UV100E series

Page 1: ...ent Reduced power consumption and extended bulb life Communicates with other home appliances through Enviracom three wire communications bus Automatic brownout and high temperature protection for UV lamps Return air models supplied with integrated airflow sensor to monitor air flowing through ductwork Dual purpose reset button Commands lamp on with a single one second push Resets internal lamp run...

Page 2: ...em is mounted in the supply side air duct or downstream or upstream from air conditioner evaporator coils in HVAC system It reduces mold growth and spores on duct surfaces coils and drip pans Does not use an airflow sensor Without Enviracom hooked up operates steady on off cycle lamp operates three hours on three hours off for a total two year life cycle With Enviracom hooked up after initial thre...

Page 3: ...aviolet light to be seen after installation Do not attempt to bypass duct mount switch CAUTION Personal Injury Hazard Power supply can cause electrical shock Disconnect power supply before beginning installation Do not open base unit or lamp handle there are no user serviceable components inside Selecting Mounting Location CAUTION Equipment Damage Hazard Ultraviolet light can cause color shift or ...

Page 4: ... Mount to allow correct operation a Do not mount upside down b Do not mount with lamps facing up CAUTION Sharp Edges Hazard Can cause personal injury Be careful when inserting ultraviolet device into sheet metal cutout Wear protective gloves when working near sheet metal Duct Mounting Use the following instructions to mount the UV System on the air duct of an HVAC system 1 Disconnect power to the ...

Page 5: ...25 7 178 3 1 2 89 4 102 14 7 8 379 M20190A SURFACE TREATMENT SYSTEM 2 1 4 57 3 1 2 89 4 1 2 114 7 178 1 25 7 178 3 1 2 89 4 102 7 7 16 188 AIR TREATMENT SYSTEM SINGLE LAMP 1 2 12 M20191A 3 1 2 89 5 127 7 178 10 254 2 3 16 56 8 1 2 216 3 1 4 83 4 102 14 7 8 379 1 2 12 M20192A 3 1 2 89 5 127 AIR TREATMENT SYSTEM DUAL LAMP ...

Page 6: ...clockwise This should cause the lamp handle to drop into the bottom of the lamp well 13 Rotate the lamp handle clockwise until it snaps into place with the lamp light indicator aligned with the raised button on the unit cover See Fig 6 Fig 6 Snap lamp handle into place WARNING UV Light Hazard Harmful to bare skin and eyes Can cause temporary or permanent loss of vision View illumination only throu...

Page 7: ... follows a Bulb life means emitting adequate amount of UV C energy to maintain an effective kill rate At 0 bulb life remaining the lamp continues to operate until catastrophic bulb failure bulb burns out but the kill rate becomes rapidly negligible Installer should also orient the homeowner to the reset button on the bottom of the UV system that when pressed briefly for one second can be used to c...

Page 8: ... longer only when replacing the bulb MAINTENANCE How You Can Maintain Your UV System You should regularly clean your ultraviolet lamp to maintain peak effectiveness of your air treatment or surface treatment system Replace the ultraviolet bulb when the LED status light on the front of your UV System is on steadily CAUTION Personal Injury Hazard Power supply can cause electrical shock Disconnect po...

Page 9: ...tinue pushing and gently rotating counterclockwise until the lamp handle inserts fully into the base See Fig 14 Fig 14 Position lamp handle for insertion back into lamp base 8 Rotate the lamp handle clockwise until it snaps into place with the lamp light indicator aligned with the raised but ton on the unit cover See Fig 15 Fig 15 Snap lamp handle into place WARNING UV Light Hazard Harmful to bare...

Page 10: ... SnapLamp handle 7 Insert the lamp handle into the base with the lamp light indicator at the eleven o clock position Continue pushing and gently rotating counterclockwise until the lamp handle inserts fully into the base See Fig 4 8 Rotate the lamp clockwise until it snaps into place with the lamp light indicator aligned with the raised button on the unit cover See Fig 6 9 Reconnect power to your ...

Page 11: ... Handle Assembly Replacement Bulb UV100E1043 Air Treatment System single lamp left photo UC100E1006 UC18W1004 UV100E3007 Surface Treatment System center photo UC100E1030 UC36W1006 UV100E2009 Air Treatment System dual lamp right photo UC100E1030 two required UC36W1006 two required M18621B ...

Page 12: ...on next page Fig 19 Air Treatment System dual lamp template M20194A CENTER OF 2 IN 51 MM HOLE FOR LAMP 1 1 2 IN 38 HOLE FOR AIRFLOW SENSOR CENTER OF AIRFLOW SENSOR HOLE 3 32 IN 3 MM PILOT HOLES FOR MOUNTING SCREWS ALIGN EITHER OF THESE LINES AS CLOSE AS POSSIBLE TO DUCT CENTER LINE INSTALLATION TEMPLATE FOR AIR TREATMENT SYSTEM SINGLE LAMP ...

Page 13: ...MP 3 32 IN 3 MM PILOT HOLES FOR MOUNTING SCREWS ALIGN EITHER OF THESE LINES AS CLOSE AS POSSIBLE TO DUCT CENTER LINE INSTALLATION TEMPLATE FOR AIR TREATMENT SYSTEM DUAL LAMP 3 32 IN 3 MM PILOT HOLES FOR MOUNTING SCREWS CENTER OF AIRFLOW SENSOR HOLE 1 1 2 IN 38 HOLE FOR AIRFLOW SENSOR ...

Page 14: ... 20 Surface Treatment System template M20193A CENTER OF 2 IN 51 MM HOLE FOR LAMP 3 32 IN 3 MM PILOT HOLES FOR MOUNTING SCREWS ALIGN EITHER OF THESE LINES AS CLOSE AS POSSIBLE TO DUCT CENTER LINE INSTALLATION TEMPLATE FOR SURFACE TREATMENT SYSTEM ...

Page 15: ...UV100E ULTRAVIOLET SYSTEMS 15 68 0262 5 ...

Page 16: ...nc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com UV100E ULTRAVIOLET SYSTEMS U S Registered Trademark 2007 Honeywell International Inc 68 0262 5 M S Rev 03 07 ...

Reviews: