PRODUCT DATA

68-0045-3

® U.S. Registered Trademark
Copyright © 2001 Honeywell •  All Rights Reserved 

V8200

Combination Gas Controls

APPLICATION

The V8200 Continuous Pilot Combination Gas Controls are 

used in gas-fired, standing pilot appliances. The include a 
manual gas valve, safety shutoff, single automatic operator 

and a pressure regulator.

FEATURES

• Add ECO switch where codes call for dual safety 

shutoff.

• For use with 24 Vac heating appliances that burn 

natural or liquefied petroleum (LP) gas.

• Capacity rated at 130 feet

3

/hour at 1 inch wc pressure 

drop (3.7m

3

/hr at 0.25 kPa). Maximum regulated 

capacity is 200 feet

3

/hour (5.7 meter

3

/hour). Minimum 

regulated capacity is 20 feet

3

/hour (.6 meter

3

/hour).

• Diaphragm-operated automatic valve opens under 

control of the regulator and closes if gas or power 

supply is interrupted.

• Three-position manual gas control knob has ON, OFF, 

and PILOT positions.Separate reset button must be 

held down to permit gas flow while lighting pilot; can 

be pushed down only in PILOT positions. All 
adjustments, wiring connections and pilot outlet are 

accessible from the top of the gas control.

• Compact size.
• Straight-through body pattern right angle adapters 

available for inlet and outlet.

• 1/2 inch inlet and 1/2 inch outlet; adapters available 

for 3/8 or 3/4 inch inlet or outlet.

• Adjustable servo regulator effectively maintains 

almost constant gas output pressure under wide 
fluctuations in gas supply pressure. Factory setting 

does not need readjustment for specific rating of 

furnace.

• Inlet and outlet screens included.
• Pilot filter included.
• Wiring terminal block color-coded beige to identify 

standing pilot models.

• May be installed at any angle between 0 and 90 degrees 

from the upright position, including vertically.

• 1/4 inch quick-connect terminals for electrical 

connections.

• 0°F to 175°F (-18°C to +79°C) temperature range 

standard; -40°F to +175°F (-40°C to +79°C) available.

• Inlet and outlet pressure taps included; both taps 

accessible from top of gas control.

• Standard, slow, and step-opening models available.
• ECO connector included with some models:  also 

available as accessory.

• Natural to LP gas conversion kit included with 

standard and slow-opening models.

• LP to natural gas conversion kit available for standard 

and slow-opening models.

Contents

Application .......................................................................

1

Features ...........................................................................

1

Specifications ...................................................................

2

Ordering Information ........................................................

2

Installation ........................................................................

4

Startup and Checkout  ......................................................

9

Maintenance .................................................................... 11

Operation ......................................................................... 12
Service ............................................................................. 15

Instructions to the Homeowner  ........................................ 15

Summary of Contents for V8200

Page 1: ...ize Straight through body pattern right angle adapters available for inlet and outlet 1 2 inch inlet and 1 2 inch outlet adapters available for 3 8 or 3 4 inch inlet or outlet Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure Factory setting does not need readjustment for specific rating of furnace Inlet and outlet s...

Page 2: ...0A7001 include an ECO connector Part No 394332 that has two 1 4 inch quick connect terminals Electrical Ratings Supply Voltage 24 Vac 60 Hz Power Unit Hold in current 300 mA maximum Drop out current 250 to 90 mA Thermocouple Nominal output 30 mV 0 018 ohms Open Circuit Turndown Voltage 2 mV Electrical Connections 1 4 inch male quick connects Two convenience terminals on top of control optional Ter...

Page 3: ...nge Kits include one flange with attached O ring four mounting screws 9 64 inch hex wrench and instruction sheet Pressure Rating AGA rating 1 2 psi 3 5 kPa inlet pressure Pressure Regulation See Table 1 Regulator adjustment accessible from top of gas control Mounting Can be mounted 0 to 90 degrees in any direction from the upright position of the manual gas control knob including vertically Temper...

Page 4: ...ce manufacturer s instructions if available otherwise use the instructions provided below Convert Between Natural and LP Gas WARNING Fire or Explosion Hazard Can cause serious injury death or property damage 1 Do not use a gas control set for natural gas on an LP gas system or a gas control set for LP gas on natural gas system 2 When making conversion main pilot burner orifices MUST be changed to ...

Page 5: ...s the overall length of the gas control Fig 4 Install flange to gas control Choose Gas Control Location Do not locate the gas control where it may be affected by steam cleaning high humidity dripping water corrosive chemicals dust or grease accumulation or excessive heat To ensure proper operation follow these guidelines 1 Locate gas control in a well ventilated area 2 Mount gas control high enoug...

Page 6: ...the connection 2 Square off and remove burrs from end of tubing 3 Unscrew compression fitting from the pilot outlet Fig 2 Slip the compression fitting over the tubing and slide out of the way NOTE When replacing a gas control cut off old compression fitting and replace with the new compression fitting provided on the gas control Never use the old compression fitting as it may not provide a gas tig...

Page 7: ...Never use pipe compound Tighten only 1 4 turn beyond finger tight to give good electrical continuity Do not overtighten Fig 9 Installing thermocouple and optional ECO connector to the power unit APPLY WRENCH FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WRENCH TO FLANGE ONLY WHEN FLANGE IS USED M3079 GAS CONTROL TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT FITTI...

Page 8: ... terminals on the ECO connector Table 5 Maximum Length of Supplementary Limit Leadwires when using Q340A Thermocouple Table 6 Maximum Length of Supplementary Limit Leadwires when using Q309A Thermocouple L1 HOT L2 1 24V THERMOSTAT OPTIONAL CONVENIENCE TERMINALS TH TR TH TR GAS CONTROL TERMINALS HIGH LIMIT CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DO NOT J...

Page 9: ...which could cause flashback in the appliance vestibule Light the main burner 4 With the main burner in operation paint all pipe joints including adapters and gas control inlet and outlet with rich soap and water solution 5 If a gas leak is detected tighten adapter screws joints and pipe connections 6 Replace the part if gas leak can not be stopped Light the Pilot Burner Flame 1 Turn the gas contro...

Page 10: ...e pressure regulator adjustment cap and screw b Using a screwdriver turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to ensure proper operation 4 If the desired outlet gas pressure or gas flow rate cannot be achieved by adjusting the gas control check the gas control inlet pressure u...

Page 11: ...em The maintenance program should include regular checkout of the gas control as outlined under Startup and Checkout and the control system as described in the appliance manufacturer s literature Maintenance frequency must be determined individually for each application Some considerations are Cycling frequency Appliances that may cycle 100 000 times annually should be checked monthly Intermittent...

Page 12: ... valve diaphragm spring pressure and the lack of outlet pressure hold the automatic valve firmly closed blocking main burner gas flow When Thermostat Calls for Heat The gas control allows pilot and main burner gas flow during the thermostat ON cycle as shown in Fig 13 When the thermostat calls for heat the magnetic valve operator is energized and lifts the automatic operator valve disc off its sea...

Page 13: ...er may relight at the full flow rate Slow Opening Pressure Regulation V8200H Slow opening gas controls function the same as standard models except that when the thermostat calls for heat the automatic valve opens gradually Opening is slowed because a gas flow restrictor in the passage from the automatic operator slows the rate at which gas pressure is reduced under the automatic valve diaphragm af...

Page 14: ... thermocouple current drops and the power unit drops out closing the safety shutoff valve When pilot flame goes out When pilot flame goes out or is too small to reliably light the main burner thermocouple output drops below the power unit hold in value The power unit drops out closing the safety valve and stopping all gas flow through the control With the loss of outlet pressure the automatic valv...

Page 15: ...istance If above 11 ohms replace the gas control If the Main Burner Will Not Come On With a Call for Heat 1 Ensure the gas control knob is in the ON position 2 Adjust the thermostat several degrees above room temperature 3 Use an ac voltmeter to measure the voltage across terminals TH and TR If a No voltage is present check the control circuit for proper operation b 24 Vac is present but first ope...

Page 16: ... continue with the next step 6 Remove the pilot burner access panel located below and behind the gas control 7 Find the pilot burner by following the metal tube from the gas control The pilot burner is between the two burner tubes behind the pilot burner access panel 8 Turn the gas control knob counterclockwise to PILOT 9 Push and hold the gas control knob all the way in Immediately light the pilo...

Reviews: