background image

V8200 COMBINATION GAS CONTROLS

68-0045—3

10

Check and Adjust Gas Input to Main Burner

CAUTION

Equipment Damage Hazard.
Can cause equipment damage or incomplete 

combustion.

1. Do not exceed the input rating stamped on the 

appliance nameplate, or manufacturer’s 

recommended burner orifice pressure for the size 

orifice(s) used. Ensure the main burner primary air 
supply is properly adjusted for complete combustion 

(refer to the appliance manufacturer’s instructions).

2. If Checking Gas Input by Clocking the Gas Meter: 
 •  Ensure that the only gas flow   through the meter  is                      

that of the appliance being tested. 

  •  Ensure that other appliances are turned off and                     

that their pilot burners are extinguished (or                     

deduct their gas consumptions from the                       

meter reading).

 • Convert the flow rate to Btuh as described in the 

Gas Controls Handbook (form number                     

70-2602) and compare to the Btuh input rating on 
the appliance nameplate.

3. If Checking Gas Input with a Manometer (Pressure 

Gauge):

• Ensure the gas control knob is in the PILOT position 

before removing the outlet pressure tap plug to 

connect the manometer.

• Turn the gas control knob back to PILOT when 

removing the manometer and replacing outlet 

pressure tap plug. 

• Shut off the gas supply at the appliance service 

valve or, for LP gas, at the gas tank before 
removing the outlet pressure tap plug and before 

disconnecting the manometer and replacing the 

outlet pressure tap plug.

• Perform the Gas Leak Test at the inlet pressure tap 

plug.

Standard-Opening and Slow-Opening 
Pressure Regulator

1.

The gas control outlet pressure should match the 
manifold pressure listed on the appliance nameplate.

2.

With the main burner operating, check the gas control 

flow rate using the meter clocking method or check the 
gas pressure using a manometer connected to the gas 

control outlet pressure tap. Refer to Fig. 2.

3.

If necessary, adjust the pressure regulator to match the 
appliance rating. Refer to Table 7 or 8 for the factory set 

nominal outlet pressures and adjustment ranges.

a. Remove the pressure regulator adjustment cap and 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise

 to increase or 

counterclockwise

   to decrease the main 

burner gas pressure.

c. Always replace the cap screw and tighten firmly to 

ensure proper operation.

4.

If the desired outlet gas pressure or gas flow rate 

cannot be achieved by adjusting the gas control, check 
the gas control inlet pressure using a manometer at the 

inlet pressure tap. If the inlet pressure is in the normal 

range (refer to Table 7 or 8), replace the gas control. 
Otherwise, take the necessary steps to provide proper 

gas pressure to the gas control.

Step-Opening Pressure Regulator

1.

The gas control outlet pressure should match the 

manifold pressure listed on the appliance nameplate. 

2.

With main burner operating, check the gas control flow 

rate using the meter clocking method or check the gas 

pressure using a manometer connected to the gas 
control outlet pressure tap. Refer to Fig. 2.

3.

If necessary, adjust the pressure regulator to match the 

appliance rating. Refer to Table 7 or 8 for factory set 
nominal outlet pressures and adjustment ranges.

a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise

 to increase or 

counterclockwise

 to decrease the main burner 

gas pressure.

c. Always replace the cap screw and tighten firmly to 

ensure proper operation.

4.

If desired outlet pressure or flow rate cannot be 

achieved by adjusting the gas control, check the inlet 

pressure using a manometer at inlet pressure tap or 
upstream of the gas control. If the inlet pressure is in the 

normal range (refer to Table 7 or 8), replace the existing 

gas control. Otherwise, take the necessary steps to 
provide proper gas pressure to the gas control.

5.

Carefully check main burner lightoff at the step 

pressure. Ensure the main burner lights smoothly and 
without flashback to the orifice and that all ports remain 

lit. Cycle the main burner several times, allowing at least 

30 seconds between cycles for the regulator to resume 
the step function. Repeat after allowing main burner to 

cool. Readjust the full rate outlet pressure if necessary 

to improve lightoff characteristics.

Summary of Contents for V8200

Page 1: ...ize Straight through body pattern right angle adapters available for inlet and outlet 1 2 inch inlet and 1 2 inch outlet adapters available for 3 8 or 3 4 inch inlet or outlet Adjustable servo regulator effectively maintains almost constant gas output pressure under wide fluctuations in gas supply pressure Factory setting does not need readjustment for specific rating of furnace Inlet and outlet s...

Page 2: ...0A7001 include an ECO connector Part No 394332 that has two 1 4 inch quick connect terminals Electrical Ratings Supply Voltage 24 Vac 60 Hz Power Unit Hold in current 300 mA maximum Drop out current 250 to 90 mA Thermocouple Nominal output 30 mV 0 018 ohms Open Circuit Turndown Voltage 2 mV Electrical Connections 1 4 inch male quick connects Two convenience terminals on top of control optional Ter...

Page 3: ...nge Kits include one flange with attached O ring four mounting screws 9 64 inch hex wrench and instruction sheet Pressure Rating AGA rating 1 2 psi 3 5 kPa inlet pressure Pressure Regulation See Table 1 Regulator adjustment accessible from top of gas control Mounting Can be mounted 0 to 90 degrees in any direction from the upright position of the manual gas control knob including vertically Temper...

Page 4: ...ce manufacturer s instructions if available otherwise use the instructions provided below Convert Between Natural and LP Gas WARNING Fire or Explosion Hazard Can cause serious injury death or property damage 1 Do not use a gas control set for natural gas on an LP gas system or a gas control set for LP gas on natural gas system 2 When making conversion main pilot burner orifices MUST be changed to ...

Page 5: ...s the overall length of the gas control Fig 4 Install flange to gas control Choose Gas Control Location Do not locate the gas control where it may be affected by steam cleaning high humidity dripping water corrosive chemicals dust or grease accumulation or excessive heat To ensure proper operation follow these guidelines 1 Locate gas control in a well ventilated area 2 Mount gas control high enoug...

Page 6: ...the connection 2 Square off and remove burrs from end of tubing 3 Unscrew compression fitting from the pilot outlet Fig 2 Slip the compression fitting over the tubing and slide out of the way NOTE When replacing a gas control cut off old compression fitting and replace with the new compression fitting provided on the gas control Never use the old compression fitting as it may not provide a gas tig...

Page 7: ...Never use pipe compound Tighten only 1 4 turn beyond finger tight to give good electrical continuity Do not overtighten Fig 9 Installing thermocouple and optional ECO connector to the power unit APPLY WRENCH FROM TOP OR BOTTOM OF GAS CONTROL TO EITHER SHADED AREA WHEN FLANGE IS NOT USED APPLY WRENCH TO FLANGE ONLY WHEN FLANGE IS USED M3079 GAS CONTROL TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT FITTI...

Page 8: ... terminals on the ECO connector Table 5 Maximum Length of Supplementary Limit Leadwires when using Q340A Thermocouple Table 6 Maximum Length of Supplementary Limit Leadwires when using Q309A Thermocouple L1 HOT L2 1 24V THERMOSTAT OPTIONAL CONVENIENCE TERMINALS TH TR TH TR GAS CONTROL TERMINALS HIGH LIMIT CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DO NOT J...

Page 9: ...which could cause flashback in the appliance vestibule Light the main burner 4 With the main burner in operation paint all pipe joints including adapters and gas control inlet and outlet with rich soap and water solution 5 If a gas leak is detected tighten adapter screws joints and pipe connections 6 Replace the part if gas leak can not be stopped Light the Pilot Burner Flame 1 Turn the gas contro...

Page 10: ...e pressure regulator adjustment cap and screw b Using a screwdriver turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to ensure proper operation 4 If the desired outlet gas pressure or gas flow rate cannot be achieved by adjusting the gas control check the gas control inlet pressure u...

Page 11: ...em The maintenance program should include regular checkout of the gas control as outlined under Startup and Checkout and the control system as described in the appliance manufacturer s literature Maintenance frequency must be determined individually for each application Some considerations are Cycling frequency Appliances that may cycle 100 000 times annually should be checked monthly Intermittent...

Page 12: ... valve diaphragm spring pressure and the lack of outlet pressure hold the automatic valve firmly closed blocking main burner gas flow When Thermostat Calls for Heat The gas control allows pilot and main burner gas flow during the thermostat ON cycle as shown in Fig 13 When the thermostat calls for heat the magnetic valve operator is energized and lifts the automatic operator valve disc off its sea...

Page 13: ...er may relight at the full flow rate Slow Opening Pressure Regulation V8200H Slow opening gas controls function the same as standard models except that when the thermostat calls for heat the automatic valve opens gradually Opening is slowed because a gas flow restrictor in the passage from the automatic operator slows the rate at which gas pressure is reduced under the automatic valve diaphragm af...

Page 14: ... thermocouple current drops and the power unit drops out closing the safety shutoff valve When pilot flame goes out When pilot flame goes out or is too small to reliably light the main burner thermocouple output drops below the power unit hold in value The power unit drops out closing the safety valve and stopping all gas flow through the control With the loss of outlet pressure the automatic valv...

Page 15: ...istance If above 11 ohms replace the gas control If the Main Burner Will Not Come On With a Call for Heat 1 Ensure the gas control knob is in the ON position 2 Adjust the thermostat several degrees above room temperature 3 Use an ac voltmeter to measure the voltage across terminals TH and TR If a No voltage is present check the control circuit for proper operation b 24 Vac is present but first ope...

Page 16: ... continue with the next step 6 Remove the pilot burner access panel located below and behind the gas control 7 Find the pilot burner by following the metal tube from the gas control The pilot burner is between the two burner tubes behind the pilot burner access panel 8 Turn the gas control knob counterclockwise to PILOT 9 Push and hold the gas control knob all the way in Immediately light the pilo...

Reviews: