V8200 COMBINATION GAS CONTROLS
68-0045—3
2
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1.
Your local Home and Building Control Sales Office (check white pages of your phone directory).
2.
Home and Building Control Customer Relations
Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
SPECIFICATIONS
IMPORTANT:
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not match the listed specifications
exactly. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
Standard Models
Models:
V8200 Continuous Pilot Combination Gas Controls. For
use in standing pilot appliances. See Table 1 for model
specifications. Models with a 7 following the suffix letter,
i.e., V8200A7001, include an ECO connector (Part
No. 394332) that has two 1/4 inch quick-connect terminals.
Electrical Ratings:
Supply Voltage: 24 Vac, 60 Hz.
Power Unit:
Hold-in current: 300 mA maximum.
Drop-out current: 250 to 90 mA.
Thermocouple:
Nominal output: 30 mV (0.018 ohms).
Open Circuit Turndown Voltage: 2 mV.
Electrical Connections:
1/4 inch male quick-connects.
Two convenience terminals on top of control (optional).
Terminal block color-coded beige.
Thermostat Heat Anticipator Setting: 0.30A.
Type of Gas:
V8200 set up for natural gas includes a 393691 LP
Conversion Kit.
Kit for conversion from LP to natural gas is available for
standard and slow opening models. See Accessories.
Table 1. Model Specifications.
Model No.
Suffix
Letter
Opening
Characteristic
Type
of Gas
Standard Factory
Regulator Settings
Ranges of Optional Factory
Regulator Settings
Range of Field
Adjustment
In. wc
Kpa
in. wc
kPa
in. wc
kPa
A,M
Standard
Opening
Natural 3.5
0.9
3 to 5
0.7 to 1.2
3 to 5
0.7 to 1.2.
LP
10.0
2.5
8 to 12
2 to 3
8 to 12
2 to 3.
C
Step-opening
Natural 0.9 step
(50% of full
rate); 3.5 full
rate.
0.2 step
(50% of full
rate); 0.9 full
rate.
Step: 0.7, 0.9, 1.2
or 1.7, as
ordered.
Full Rate: 3 to 5
Step: 0.17, 0.22,
0.30 or 0.48, as
ordered.
Full Rate: 0.7 to 1.2
Step:
none.
Full Rate:
3 to 5.
Step:
none.
Full Rate:
0.7 to 1.2.
LP
2.2 step
(45% of full
rate); 10 full
rate.
0.5 step
(45% of full
rate); 2.5 full
rate.
Step: 1.4, 2.5, 4.0
or 5.5, as
ordered.
Full Rate: 8 to 12.
Step: 0.35, 0.62,
0.99 or 1.37, as
ordered.
Full Rate: 2 to 3.
Step:
none.
Full Rate:
8 to 12.
Step:
none.
Full Rate:
2 to 3.
H
Slow-opening
Natural 3.5
0.9
3 to 5
0.7 to 1.2
3 to 5
0.7 to 1.2
LP
10.0
2.5
8 to 12.
2 to 3
8 to 12
2 to 3