background image

69-0329—4

2

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH.
Follow these warnings exactly:
1. Disconnect power supply before wiring to pre-

vent electrical shock or equipment damage.

2. To avoid dangerous accumulation of fuel gas,

turn off gas supply at the appliance service val-
ve before starting installation, and perform
Gas Leak Test after completion of installation.

3. Always install sediment trap in gas supply line

to prevent contamination of gas control.

4. Do not force the gas control knob. Use only

your hand to turn the gas control knob. Never
use any tools. If the gas control knob will not
operate by hand, the gas control should be
replaced by a qualified service technician.
Force or attempted repair may result in fire or
explosion.

CAUTION

CAUTION

Never apply a jumper across or short the valve
coil terminals. This may burn out the heat antici-
pator in the thermostat or damage the electronic
direct ignition (DI) module.

IMPORTANT: These gas controls are shipped with pro-

tective seals over inlet and outlet tappings. Do not
remove seals until ready to connect piping.

Follow the appliance manufacturer instructions if avail-

able; otherwise, use the instructions provided on the fol-
lowing pages.

CONVERTING BETWEEN NATURAL AND  LP
GAS

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY OR DEATH.
1. Do not use a gas control set for natural gas on

an LP gas system or a gas control set for LP gas
on a natural gas system.

2. When making conversion, main pilot burner

orifices  must  be changed to meet appliance
manufacturer specifications.

Refere to appliance manufacturer instructions for orifice

specifications and changeover procedure.  Gas controls are
factory-set for natural (and manufactured) or LP gas. Do
not attempt to use a control set for natural (manufactured)
gas on LP gas, or a control set for LP on natural (manufac-
tured) gas.

Gas controls with standard or slow opening regulators

can be converted from one gas to the other with a conver-
sion kit (ordered separately). Order part no. 393691 to
convert from natural (manufactured) to LP gas; order part
no. 394588 to convert from LP to natural (manufactured)
gas. Controls with step opening regulators cannot be con-
verted.

INSTALL ADAPTERS TO CONTROL

If adapters are to be installed on the gas control, mount

them as follows:

Flanges:

1. Choose the appropriate flange for your application.
2. Remove seal over control inlet or outlet.
3. Assure O-ring is fitted in the groove of flange. If the

O-ring is not attached or is missing, do not use flange.

4. With O-ring facing control, align the screw holes on

the control with the holes in the flange. Insert and tighten
the screws provided with the flange. See Fig. 1. Tighten the
screws to 25 inch pounds of torque to provide a gas-tight
seal.

Fig. 1—Fasten flange to valve firmly, but do
not overtighten screws.

!

Bushings:

1. Remove seal over control inlet or outlet.
2. Apply moderate amount of good quality pipe com-

pound to bushing, leaving two end threads bare. On LP
installation, use compound resistant to LP gas. Do not use
Teflon tape.

3. Insert bushing in control and carefully thread pipe

into bushing until tight.

Complete instructions below for piping, installing con-

trol, and wiring. Make certain the leak test you perform on
the control after completing the installation includes leak
testing the adapters and screws. If you use a wrench on the
valve after flanges are installed, use the wrench only on the
flange, not the control. Refer to Fig. 5.

M9046

VALVE OUTLET

FLANGE

9/64 INCH HEX SCREWS (4) 

DO NOT OVERTIGHTEN SCREWS.  TIGHTEN TO 
25 INCH-POUNDS.

1

1

!

!

Summary of Contents for V8205

Page 1: ...0 6 393690 16 Elbow 393690 3 393690 13 3 4 in NPT Straight 393690 4 393690 14 Elbow 393690 5 393690 15 Model No Suffix Letter Ambient Temperature Range Regulator Type A 0 F to 175 F Standard 18 C to 79 C C Step opening H Slow opening K 40 F to 175 F 40 C to 79 C M Standard P Step opening Model Voltage Frequency Number of Automatic Operators Gas Control Knob Positions Current Draw V8205 24V 60 Hz O...

Page 2: ... controls are factory set for natural and manufactured or LP gas Do not attempt to use a control set for natural manufactured gas on LP gas or a control set for LP on natural manufac tured gas Gas controls with standard or slow opening regulators can be converted from one gas to the other with a conver sion kit ordered separately Order part no 393691 to convert from natural manufactured to LP gas ...

Page 3: ...y direction from the upright position of the gas control knob including vertically 2 Mount the control so gas flow is in the direction of the arrow on the bottom of the control 3 Thread pipe into control Do not thread pipe to far Valve distortion or malfunction may result if the pipe is inserted too deeply refer to Table 4 TABLE 4 NPT PIPE THREAD LENGTH IN in OUTLET PRESSURE TAP INLET OUTLET WIRIN...

Page 4: ...age 1 Check the power supply rating on the gas control and make sure it matches the available supply Install the trans former thermostat and other controls as required 2 Connect control circuit to gas control terminals See Figs 4 6 and 7 3 Adjust thermostat heat anticipator to 0 50A rating stamped on valve operator Fig 7 Wiring connections for 24 volt control in S89 direct ignition system WHITE BL...

Page 5: ...operly adjusted for complete combustion Followinstructionsofappliancemanufacturer 2 IF CHECKING GAS INPUT BY CLOCK ING GAS METER Make certain there is no gas flow through the meter other than to the appliancebeingchecked Otherappliancesmust remain off with their pilots extinguished or their consumption must be deducted from the meter reading Convert flow rate to Btuh as described in Gas Controls H...

Page 6: ...htoff characteristics TABLE 5A PRESSURE REGULATOR SPECIFICATION PRESSURES IN kPa CHECK SAFETY LOCKOUT SLOW OPENING CONTROLS ONLY 1 With the system power off and the thermostat set to call for heat manually shut off the gas supply 2 Energize ignitor control and start timing safety lock out time When spark ignition terminates stop timing When using the VR8205H step opening control the specified igni...

Page 7: ...PERSONAL INJURY OR LOSS OF LIFE 1 Before lighting smell around the appliance area for gas If the appliance uses LP bottled gas be sure to smell next to the floor because LP gas is heavier than air If you smell gas immediately shut off the manual valve in the gas piping to the appliance or on LP at the tank Do not try to light any appliance Do not touch any electrical switch or use the phone Leave ...

Page 8: ... LP installation immediately shut off the manual valve in the gas piping to the appliance or on LP at the tank Don t touch any electrical switch or use the phone Leave the building and call your gas supplier If your gas supplier cannot be reached call the fire department Failure to do so may result in fire or explosion 6 If you don t smell gas turn knob on gas control counterclockwise to ON 7 Repl...