V9055A,D MODULATING FLUID POWER GAS VALVE ACTUATOR

7. If the valve bonnet assembly is in good condition and is 

not replaced, replace the bonnet seal. Do not reuse the 

old bonnet seal. See Table 6 below for the seal number.

8. Coat seals with grease provided and position in valve 

body/bonnet assembly.

9. Carefully seat the bonnet assembly on the valve body. 

Be sure the seals are in their proper position. On those 

valves with a spring below the disc, be sure the spring is 

centered in the indentation on the inside of the valve 

body.

10. After positioning the bonnet assembly, replace the 

screws removed earlier. 

NOTE: When replacing the bonnet assembly on the 4-

inch valve, draw it evenly into the valve body. 

Finger-tighten the eight bolts. Draw the bonnet 

assembly into the valve by tightening, in order, 

bolts 1, 5, 7 and 3 (two turns each). Repeat 

until the bonnet assembly is seated. Tighten 

the remaining bolts. Torque the bolts as

follows:

11. Remount the actuator on the bonnet assembly. Tighten 

the two set screws (50-60 inch pounds).

12. Replace the damper crank arm assembly.

13. Re-attach the wires removed from the actuator termi-

nals and turn on the electrical power.

14. With the gas still off, cycle the actuator to check for 

proper mechanical operation.

CAUTION

Be sure to perform a bonnet seal and seat leak check 

after installation.

Be sure to read and follow all instructions that come 

with the actuators, valves, seal and bonnet kits.

**Each replacement assembly contains the bonnet assembly, 

two rubber seals, and a tube of grease. It must be used only 

on the type of valve indicated above.

Valve Size

Torque

3/4 in. (19 mm) to 1-1/2 in. (38 mm)

55 in.-lb.

2 in. (51 mm) to 4 in. (102 mm)

75 in.-lb.

Table 5. Replacement Bonnets for

V5055/V5097 Gas Valves.

Replacement 

Bonnet**

Valve

Valve Size (in 

inches)

133398AA

V5055A

V5097A

3/4, 1, 1-1/4, 1-1/2

133417AA

2, 2-1/2, 3

Not Available

(On-Off)

4

133398BA

V5055B

V5097B

3/4, 1, 1-1/4, 1-1/2

133417BA

2, 2-1/2, 3

Not Available

(Characterized Guide)

4

133398CA

V5055C

V5097C

3/4, 1, 1-1/4, 1-1/2

133417CA

2, 2-1/2, 3

136911CA

(Proof of Closure)

4

Not Available

V5055D

V5097D

3/4, 1, 1-1/4, 1-1/2

Not Available

2, 2-1/2, 3

136308BA

V5055E

V5097E

3/4, 1, 1-1/4, 1-1/2

Not Available

2, 2-1/2, 3

Table 6. Gas Valve Replacement Seals.

Replacement Seal 

Assy #

Valve Size (in inches.)

133393A

3/4, 1, 1-1/4, 1-1/2

133392A

2, 2-1/2, 3

137253A

4

Summary of Contents for V9055A

Page 1: ...e for 60 Hz models is 40 F to 125 F 40 C to 53 C Ambient temperature range for 50 Hz and 50 60 Hz models is 10 F to 125 F 23 C to 52 C Auxiliary 1 2 hp rated switch is available for field installation Integral damper shaft provides a maximum of 20 lb 9 kg of force Valve and actuator may be mounted in any position Model is available with NEMA 4 IP54 weatherproof enclosure V9055D V5055C E and V9055D...

Page 2: ...capacity curves Table 1 Pressure Ratings of Actuator Valve Combinations a Max Operating Pressure Differential UL or Max Operating Pressure CSA maximum allowable pressure drop from inlet to outlet for proper operation b Max rated pressure UL or Max Close off Pressure CSA maximum pressure that the valve can be exposed to without leak age or damage to the valve c Applies for small body V5097 valves 3...

Page 3: ... 3 32 5 KNOCKOUT FOR1 2 INCH CONDUIT 4 OCTAGON 3 4 19 1 BOLT HOLES 8 ON 3 3 4 95 RADIUS 1 9 32 1 3 16 30 9 3 16 233 27 32 21 5 3 23 32 5 94 5 127 0 3 19 32 91 6 3 4 171 5 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 VALVE SIZE INCH 11 1 8 11 1 8 11 1 8 11 1 8 11 1 4 11 3 4 11 3 4 14 1 8 2 3 4 2 3 4 2 3 4 2 3 4 2 7 8 3 3 8 3 3 8 5 13 16 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 13 16 8 13 16 11 7 32 5 3 4 5 3 4 5 3 4 ...

Page 4: ...ide down if water is likely to drip on it In this position water can become trapped in the electronics compartment When Installing This Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condi tion 2 Check the ratings given in the instruction and on the product to make sure the product is suitable for your application 3 Installer must b...

Page 5: ...er crank arm is used with a NEMA 4 actuator that is exposed to ice or sleet a suitable shield must be installed to prevent ice or sleet buildup The crank arm provides a maximum travel of 2 5 16 in 59 mm For complete installation information refer to the instructions packed with the 7616BR Crank Arm Fig 2 Crank Arm Operation Fig 3 Internal components and connections in V9055 WIRING WARNING Electric...

Page 6: ...n Verify proper operation after servicing ADJUSTMENTS IMPORTANT When using the V9055D with the V5055 V5097C or E two seals Valves match low fire minimum adjust ment to the burner and the application Too low of an adjustment could result in loss of burner flame Also plan to check this low fire adjustment at periodic maintenance intervals Adjust Low Fire Setting The low fire setting is adjustable fr...

Page 7: ...al potentiometer color to color to terminals W R and B on the actuator With the valve energized use the potentiometer to open and close the actuator It should run from the low fire position and to the fully open position If the actuator fails to operate properly replace it 1 Turn off the gas supply at the manual shutoff valve located upstream from the valve s being serviced 2 Shut off all electric...

Page 8: ...ssembly 13 Re attach the wires removed from the actuator termi nals and turn on the electrical power 14 With the gas still off cycle the actuator to check for proper mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet kits Each replacement assembly contai...

Reviews: