background image

OPERATION 

Actuator 

Connection 

Valve 

Movement

Type 

Cable Model 

Molex

TM

 Model 

3-WIRE 

(for SPDT 

controller) 

Blue & Brown energised 

Black de-energized 

Pin #2 & #3 energised Pin 

#6 de-energised 

Closes 

Blue & Black energised 

Brown de-energized 

Pin #2 & #6 energised Pin 

#3 de-energised 

Opens 

2 + COM. 

(for SPST 

controller) 

Blue & Brown energised 

Black open 

Pin #2 & #3 energised Pin 

#3 & #6 open 

Closes 

Blue & Brown energised 

Black closed 

Pin #2 & #3 energised Pin 

#3 & #6 closed 

Opens 

WHEN USED WITH SPDT (3-WIRE) CONTROLLER (Figure 8):  On 
a call for heat, the NO thermostat contacts close, the valve opens. 
When the valve reaches the fully open position, the cam actuated 
SW1 closes and SW2 opens. When the need for heat is satisfied 
the NC thermostat contacts close, energizing the valve through 
SW1 to close the valve. When the valve reaches the fully close 
position, the cam actuated SW2 closes and SW1 opens anticipating 
the next call for heat cycle. 
In a power failure the valve will stay at whatever position it was in 
when the power was interrupted. When power is restored, the valve 
will  respond to the controller demand. 

AC 

MOTOR

CW 

CAM 

Valve 

Close 

Open 

"VC "HYDRONIC VALVE 

SW1 

SW2 

S.P.D.T. 

CONTROLLER 

NC 

NO 

BROWN 

BLACK 

BLUE 

Figure 8 - Actuator wiring for SPDT controller 

NOTE:

 VC2114 and VC8114 actuators must be used with sepa­

rately-powered (hardwired) electronic controllers.  Their sustained 
current draw is too low for power stealing (parasitic power) 
thermostats or series anticipators of electromechanical thermo­
stats. 

WHEN USED WITH SPST CONTROLLER  (Figure 9):  On a call for 
heat, RLY1 is energized making the NO contacts in SW3, the valve 
opens. When the valve reaches the fully open position the cam 
operated SW1 closes and SW2 opens. When need for heat is 
satisfied, 

the thermostat contacts open, RLY1 is de-energized and the valve 
motor is driven closed through  SW1 and the NC contacts of SW3. 
When the valve reaches the fully closed position, the cam operated 
SW2 closes and SW1 opens anticipating the next call for heat 
cycle. 

"VC"  HYDRONIC VALVE 

AC 

MOTOR

CW 

CAM 

RLY1 

SW1 

SW2 

Valve 

Close 

Open 

NC 

NO 

SW3 

BLUE 

BROWN 

CONTROLLER 

6

BLACK 

S.P.S.T 

Figure 9 - Actuator wiring for SPST controller 

CHECKOUT 

1. Raise the set point of the thermostat above room temperature to 

initiate a call for heat. Red valve position lever should move 
downward to the open position. 

2. For auxiliary switch models, observe all control devices. The valve 

should open and the auxiliary switch (if present) should close and 
make at the end of the opening stroke to activate auxiliary 
equipment. 

3. Lower the set point of the zone thermostat below room temperature. 
4. Observe the control devices. The valve should close and all auxiliary 

equipment should stop. 

SERVICE 

This valve should be serviced by a trained, experienced service 
technician. 

1. If the valve is leaking, drain system 

OR

 isolate valve from the 

system. 
2. Check to see if the cartridge needs to be replaced. 
3. If the motor or other internal parts of the actuator is damaged, 
replace the entire actuator assembly. 

NOTE: Honeywell hydronic valves are designed and tested for silent 
operation in properly designed and installed systems.  However, water 
noises may occur as a result of excessive water velocity. Piping noises 
may occur in high temperature (over 212

°

F [100

°

C]) systems with 

insufficient water pressure. 

Automation and Control Solutions 

In Canada: 

Environmental Control Products 

Honeywell Limited-Limitee

1985 douglas Drive North

35 Dynamic Drive

Golden Valley, MN 55422-3992

Toronto, ON M1V 4Z9 

U.S.A. 

Canada 

Printed in Canada 

Summary of Contents for VC2 Series, VC4 Series, VC60 Series, VC8Series

Page 1: ... generally accepted industry standards Honeywell is not responsible for damages resulting from misapplication or misuse of its products Voltage Label Colour Code 24V 50Hz 24V 60Hz Models Blue 100 130 V 50 60 Hz Model Black 200 240 V 50 60 Hz Model Red Power consumption 6 Watts Max at nominal Voltage during valve position change Use 24 V Class 2 transformer Provide 6 VA per valve for transformer an...

Page 2: ...pression 3 116 4 9 16 147 5 13 16 NORTH AMERICA STANDARD MODELS 3 8 FLARE 1 98 3 7 8 111 4 3 8 136 5 11 32 1 2 SWEAT 89 3 1 2 130 5 1 8 1 2 FLARE 1 98 3 7 8 136 5 11 32 1 2 INVERTED FLARE 1 1 2 NPT int 3 4 NPT int 94 3 11 16 113 4 7 16 130 5 1 8 3 4 SWEAT 132 136 5 3 16 5 11 32 1 NPT int 1 SWEAT 1 1 4 SWEAT 110 4 5 16 118 4 5 8 142 5 5 8 1 1 4 NPT int 1 No adapters 2 Suitable for use as15 mm compr...

Page 3: ...he piping The latch will click when engaged See Figure 2 NOTE The actuator can also be installed at right angles to the valve body but in this position the latch mechanism will not engage 2 Connect leadwires See Figure 3 for flexible conduit installation with plenum cable models Figure 2 Latch Mechanism to detach Actuator 4 1 2 3 3 8 flex conduit Figure 3 Flexible Conduit Attachment WIRING NOTE Ea...

Page 4: ... cam operated SW1 closes and SW2 opens When need for heat is satisfied the thermostat contacts open RLY1 is de energized and the valve motor is driven closed through SW1 and the NC contacts of SW3 When the valve reaches the fully closed position the cam operated SW2 closes and SW1 opens anticipating the next call for heat cycle VC HYDRONIC VALVE AC MOTOR CW CAM RLY1 SW1 SW2 Valve Close Open NC NO ...

Reviews: