Message Action list
The messages displayed at the
control panel, network node or loop repeat panels
are given here in an
alphanumerical
order to provide guidance:
¨
on a 'fault message'
¨
the likely meaning of the message
¨
along with suggestions on what initial actions may be taken to rectify the problem.
"
Only the messages that are applicable will appear on the display of the control panel, network node or loop repeat panels. Additionally the display will identify the panel
where the event was first detected.
¨
The term device was previously referred to as outstation.
Message
associated with..
meaning..
..possible action
A spurious FIRQ at
card x
MCC / MCB
(main control card/board)
There is glitch on the MCC hardware that appears on
the backplane / MCB.
Clear and ignore single occurrence.
A spurious IRQ at
card x
MCC / MCB
(main control card/board)
There is glitch on the MCC / MCB hardware.
Clear and ignore single occurrence.
A spurious NMI at
card x
MCC / MCB
(main control card/board)
There is glitch on the MCC / MCB hardware
.
Clear and ignore single occurrence
.
A spurious SWI2 at
card x
MCC / MCB
(main control card/board)
There is glitch on the MCC hardware.
Clear and ignore single occurrence.
A spurious SWI3
at card x
MCC / MCB
(main control card/board)
There is glitch on the MCC / MCB hardware.
Clear and ignore single occurrence.
Access fault at
card x
Any Card
Card cannot talk to the MCC / MCB local controller.
Replace card if the fault keeps reoccurring.
Could also be caused by excessive network
messages. Investigate message passing.
ACIA Failed at
card x
Network Card or
MCC / MCB
Communication chip failure or the FABs and SABs are
corrupt.
Reset the card and replace if it fault keeps
reoccurring.
Alarms silenced
MCC / MCB
(main control card/board)
Silence alarms button has been pressed.
-
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
117
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Appendix
B
-
M
essage
A
ction
L
ist