Message
associated with..
meaning..
..possible action
ASCII Device is
faulty number x on
loop y
LPC
(loop processor card)
Failure of the Control panel to communicate with
Repeat / Mimic panel. The power supplies to these
panels may not be connected.
If applicable, connect the power supply or
RESET the Master Repeat Card in the Repeat
and Mimic panel. If necessary replace the
card/software.
Back up
NVM
(non volatile memory) on
backplane or MCB
Data is being copied from cards and stored onto the
NVM.
-
Back up required
NVM
(non volatile memory) on
backplane or MCB
Data must be saved to memory
Back up data to the memory.
Battery discharged
Power supply
This indicates the failure of battery load test. The ADC
value should be equal to or less than normal - 9.
Check load test and the battery condition.
Battery disconnected/
restored
Power supply
A disconnection is indicated when the ADC value from
the battery is equal to or less than 130.
Normally it should be = 234 (27.4V)
To give a restored indication the ADC value
should = Vbatt 1/6x256/5.
Baud rate x at card y
MCC / MCB / Network Card
Baud rate set has been read.
If required, change the baud rate
.
being Initialised at
card x
NVM
(non volatile memory) on
backplane or MCB
Memory is being set up by the MCC / MCB (main
control card/board), ready for use.
-
Buffer full at card x
Any Card
Software error
.
-
Buffers out of step
at card x
Any Card
Software error.
Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Call point glass is
broken
number x loop y
Device
Call point has been operated when the device is
disabled.
Replace the glass, if necessary.
Call point on
interface unit
operated / restored
Device
Mains powered interface input has been triggered by
conventional MCP, value of input is equal to or less
than 6V.
-