Message
associated with..
meaning..
..possible action
Call point open cct
number x on loop y
Device
Monitored base does not see end-of-line unit. There is
a bad connection to MCP.
Check the internal wiring, there may be a loose
connection.
Call point
operated/restored
number x loop y
Device
Break glass has been broken or operated with a test
key.
Replace the break glass to restore the call point
or remove the test key, whichever is applicable.
Call point short cct
number x loop y
Device
Call point contacts are short circuit.
Check the call point contacts and internal
wiring.
Card found/lost at
card x
Any Card
The card has been found/lost. If lost then it is locked
out.
There may be a hardware fault on card or
backplane. Investigate and rectify.
Card n recovered
/Card n backed up
NVM
(non volatile memory) on
backplane or MCB
Data recovered to a card from the NVM. A card data
has been backed up to the NVM.
-
Chamber Removed
/Replaced number x on
loop y
Device
Device chamber has been removed.
Replacing the chamber will cause a replaced
indication.
Charger Fault
Panel
Power Supply Unit (PSU)
Charger circuit has failed.
Replace the PSU.
Charger Fault
number x on loop y
EN54 System device power
supply
(Repeat, Mimic or mains
powered interface)
Charger circuit has failed at a loop device.
Replace the board (having the power supply) on
the loop device.
Charger Restored
Panel power supply
Charger circuit is working again.
-
Charger Restored
number x on loop y
EN54 System device power
supply
(Repeat, Mimic or mains
powered interface).
Charger circuit at the loop device is working again.
-
Chk=4.874 NVMC 41874
Flag=0
NVM is write
protected at Card x
NVM
(non volatile memory) on
backplane or MCB
The memory is read only.
Disable the write protect using the [set up]
menu.
Commissioning instructions
120
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
Appendix
B
-
M
essage
A
ction
L
ist