Message
associated with..
meaning..
..possible action
Device Battery OC
number x on loop y
Device
Failure of fuse or battery wiring is OC on products like
mains powered interface unit.
Normal value = 27.4V
Value is equal to or less than 16V (OC) / greater than
17V (Restored).
Check and replace if necessary to restore.
Device Enabled /
Disabled at Card x
LPC
(loop processor card)
Device has been enabled or disabled manually or
automatically.
If necessary manually enable or disable the
device.
Device Fault number x
on loop y
ACU
Audio Control Unit
Fault input has been asserted.
Check remote equipment wired to the fault
input.
Device Gain set to x
number y on loop z
Beam devices
(can also be a Flame device -
no longer supported)
Confirmation of a change in gain setting.
-
Device inoperative
Radio (Plexus) Device
The Radio (Plexus) device batteries are too low for
device to operate correctly
Use the Battery Condition Indicator tool to
determine if the batteries in the Radio (Plexus)
Device require replacing, if necessary replace
the batteries.
Device Mains Failed /
Restored number x
loop y
Device
Failure of mains supply to mimic/repeat /mains
powered interface unit. The value of rectified DC is
equal to or less than 8V i.e. failed.
Check mains supply connections and the mains
fuse. When the rectified DC is greater than
24V it is restored.
Device Mains too high
/ low number x loop y
Devices like: Mimic / Repeat
/ Mains powered interface
unit
Failure of device mains supply.
The value of rectified DC is too high / low i.e in the
region of 30V / 17V.
Check the power supply and replace it if
necessary
Device Moved
Radio (Plexus) Device
The Radio (Plexus) device has been tampered with
The Radio (Plexus) device has been moved
from the original installed lobation or there has
been changes in the area that affect the device
operation.
Device power Fault /
Restored number x on
loop y
Device
The failure of internal power supply rail.
Replace the device.
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
123
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Appendix
B
-
M
essage
A
ction
L
ist