Fire number n loop y
channel z
LPC
(loop processor card)
Pattern match is equal to a Fire or MCP operated or
conventional detection on IO line of interface operated.
-
Fire reset
MCC / MCB
(main control card/board)
The Fire reset button has been pressed.
-
Flash memory checksum
error
Device
Speech Memory Checksum Error
Replace the device
FPE Enabled /
Disabled at card x
Device
All FPE Interface devices on loop x have been enabled
or disabled manually or automatically.
Manually enable or disable all FPE Interface
devices if required.
FPE w: x, y, z
Device
This information shows the FPE Interfaces on loop w
and are devices x, y and z.
-
Full keyboard Removed
/ Fitted number x
loop y
MCC/ MCB / DAC/ MRC
The keyboard has been ‘removed’ (is not fitted).
Check the cable connections to the keyboard to
bring about the ‘fitted’ message.
Group Enabled /
Disabled
MCC / MCB
(main control card/board)
A group has been automatically or manually disabled
or enabled.
If necessary, manually enable/disable the group
using the [control] menu.
High Error rate at
Card x
Network
High number of communication errors.
Check network wiring and connections.
Incompatible Card
Version at card x
Any Card
There is a card software conflict.
Fit card with compatible software.
Interface Failed at
card x
MCC / MCB
(main control card/board)
The interface timer chip has failed.
Clear the fault and ignore single occurrence.
Replace the card on multiple failures.
Interface input -
fault / restored
number x on
loop y channel z
Device
IO line fault.
Check the wiring and restore the input for
normal operation.
Interface Input Fire
number x on loop y
channel z
Device
Interface IO line triggered a fire event.
Check the wiring and restore the input for
normal operation.