Message
associated with..
meaning..
..possible action
Interface input not
Reset number x on
loop y channel z
Device
The input line continues to trigger.
Check devices on the IO line.
Interface Input OC /
restored
Device
The end-of-line is not seen.
Check the wiring. The device may have been
removed, if so refit the device to restore.
Interface input
operated / released
number x on loop y
channel z
Device
Fixed extinguishant interface unit input has been
triggered (applicable for old systems only).
Follow the FE system reset procedure to release
the input.
Interface input SC /
restored number x on
loop y channel z
Device
The interface wiring is short circuit. The value of input
is equal to or less than 2V.
Check the interface wiring and rectify to restore
the input.
Interface output SC
or OC or Restored
number x on loop y
channel y
Device
The value of output is equal to or less than 50% for SC
or is TBA for OC.
Check the wiring and restore the output circuit.
Intermittent Fault at
card x
Any Card
A fault has been picked up by the MCC / MCB (main
control card/board).
Replace the appropriate card if the fault keeps
reoccurring.
Invalid configuration
LPC
(loop processor card)
Loop recovered with freeblocks ON.
This is not allowed. Switch OFF the freeblocks
and reallocate.
Device
FLASH incorrectly programmed
Replace the device
Invalid configuration
at card x
LPC
(loop processor card)
Loop recovered with freeblocks ON
or Loop
configuration faulty, possibly after upload from
Commissioning Tool
.
This is not allowed. Switch OFF the freeblocks
and reallocate.
Invalid message /
reply received at
card x
LPC
(loop processor card)
The message/reply received cannot be understood. The
communication can be from a Repeat, Mimic,
Networked system.
Ignore single occurrence and record in the log
book.
Invalid message/reply
at card x
Network Card
The message/reply has not been understood from other
panels.
Ignore for single occurrence and record in the
log book.
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
127