Message
associated with..
meaning..
..possible action
NVM is read only
NVM
(non volatile memory)on
backplane or MCB
User attempts to write to a hardware write protected
NVM
Remove the hardware write protect before
writing
Panel in/out of
commissioning mode
MCC / MCB
(main control card/board)
Commissioning mode switched ON/OFF.
To manually switch commissioning mode use
the [test/eng] menu.
Panel Label Set up
MCC / MCB
(main control card/board)
Panel label has been set from the menu.
-
Panel powerup
MCC / MCB
(main control card/board)
Software reset of system or there has been a manual
reset of card 0.
If an automatic reset has occurred then check
for system errors.
Pattern number x on
loop y channel x
LPC
(loop processor card)
Sensor has detected an interesting event eg fire/fault.
-
Pointer corrupted at
card x
Any Card
Software error.
Software errors will activate a system reset.
Ignore single occurrence.
Record the event in the log book.
Pointer missing at
card x
Any Card
Software error
Software errors will cause a system reset.
Card fault should be ignored for single
occurrence.
Record the event in the log book.
Prefire number x on
loop y channel z
LPC
(loop processor card)
Pattern match less than a Fire.
-
Printer lost/fitted
at card x number y on
loop z
MCC / MCB / DAC / MRC
The external printer has not been seen and is ‘lost’.
Check the connections to the printer.
Also
check for paper jam in the printer mechanism
.
Program memory
corrupted at card x
Any Card
Checksum failure on FLASH at midnight.
Clear and ignore single occurrence.
Record in the log book.
Commissioning instructions
132
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
Appendix
B
-
M
essage
A
ction
L
ist