Message
associated with..
meaning..
..possible action
System Printer fitted
at card x number y
loop z
MCC / MCB
(main control card/board)
A 80 column serial printer is fitted to the panel.
-
System Printer Lost
at card x number y on
loop z
MCC / MCB (Printer option)
TBA
TBA
System Restarted
/Started
MCC / MCB
(main control card/board)
Link on back plane restored.
-
System stopped
MCC / MCB
(main control card/board)
Backplane link moved causing the system to stop.
The link should not be normally accessed
.
Task stuck
at card x
Any Card
Software error.
Software errors will activate a system reset.
Ignore single occurrence. Record the event in
the log book.
Test set found /
removed at card x
LPC
(loop processor card)
Remote allocation unit has been found connected to the
system.
Disconnection of the test set will bring about a
removed message.
Too many errors
number x on loop y
Device
More than 15 errors from a device in 34 hours.
Check the loop wiring to the device.
Too many errors x at
Card y
Network Card
Up to 6 consecutive communication errors.
Check wiring and cable screen. There may be
faults with the installation.
Two controller at
card x
Network
There are two network controllers.
One network controller will automatically shut
down.
Two master has the
same address at
card x
MCC / MCB / DAC
Two PCs have been given the same address.
Each PC must have a unique address.
Unable to claim
buffers at
card x
Any Card
System too busy
Wait or reset card if stuck, record in the log
book
Unrecoverable Tx
fault number x loop y
LPC
(loop processor card)
More than 3 consecutive reply errors
Check the device connections and replace if
necessary.