Setting the DKC card
The links, pot and switch on the DKC are factory configured as shown below.
Control buttons
"
The emergency control buttons must always be left in an enabled state, with the 'control
buttons' link fitted.
There is no indication given at the panel when the link is set for inactive controls.
Display Contrast
¨
The display contrast is set using the Pot RV1 on the DAC, which is factory adjusted
for optimum contrast. You can also adjust the contrast using the menu option under
[Test/Eng], see Appendix A menu maps.
"
The contrast adjustment function using the menu options may not be
applicable for some older build of panels.
Domain Address and baud rate settings
Typically the
Baud rate
set using these switches should be the same as the setting made using the
[TestEng] menu. The baud rate set must be backed up to the NVM. Where a baud rate value that
can only be achieved by [Test/Eng] menu, this must be set using the menu and backed up to NVM.
Baud Rate
Domain address
1
2
Baud 3
4
5
6
7
8
Address
Off
Off
1200
Off
Off
Off
Off
Off
Off
64
Off
On
2400
Off
Off
Off
Off
Off
On
1
On
Off
9600
Off
Off
Off
Off
On
Off
2
On
On
19200
etc
On
On
On
On
On
Off
62
On
On
On
On
On
On
63
Factory set domain address - 1 with 19200 baud (see SHADED cells)
Zone indicators
The
Zone indicators
are enabled for normal operation at an EN control panel and must NOT be
disabled.
The zone indicators are not applicable on a Network node nor on a BS Control panel. On these
products the 'zone indicator' links are set in the 'disable' position.
Commissioning instructions
26
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
Vigilon
4
/6
loop
Panels
DKC ASSEMBLY
WARNING
REMOVAL OF COVER
EXPOSES HIGH V
H VOLTAGES
Inner door assembly
Danger
RV1
Sound Alarms
Silence Alarms
Reset
Verify
Control buttons
Inner door
1
2
3
4
17
18
19
20
Zones
With Zone
indicators
(EN)
Display and
keyboard Card (DKC)
Without Zone
indicators
(BS) panel or
Network node
P6
P1
Buttons
enabled
Buttons
disabled
Factory setting
is with link fitted
8
7
6
5
4
3
2
1
ON
SW1
RV1
LCD Contrast adjust
OFF
Clockwise -
Darker
Anti-Clockwise -
Lighter
Link is NOT USED
leave link fitted.
It is for special use
with keyswitch
application