Fire Routing LEDs (post mid 2015)
The Fire Alarm Routing Equipment FARE
red
LED work with FARE Interface
configured to operate as a FARE device. The FARE LEDs illuminate to indicate the
status of FARE.
How to configure the LEDs CB253 and CB254 (pre mid 2015)
The switching of the
amber
LEDs CB253 and CB254 is controlled by
action of command builds 253 and 254 respectively. The switching action
must be configured during commissioning.
Example
This example shows how to configure the panel such that by activating an
interface input (can be a push button switch on the input), it will cause the
panel LED - CB253 and Master alarms to switch
On
. If the interface input
switch is released then the panel LED - CB253 and Master alarms will
switch
Off
.
The following procedures assume a password entry is not required.
# - will appear if a PIN is setup.
Configure the Command build trigger:
Press
Menu On/Off
button and select
[SetUp] -> [Usercode]#
, momentarily press
<etc>
to select
[SetUp]
->
[Build]
and type in the command build number
253
, select
[Trigger]
->
[IO line]
and type in the interface input
channel number, select
[Device]
and type in the interface device number, select
[Loop]
and type in the loop
number ->
[Enter]
. The command build 253 is now configured to be triggered by the interface input.
Configure the Command build label:
Press
Menu On/Off
button and select
[SetUp] -> [Usercode]#
, momentarily press
<etc>
to select
[SetUp]
->
[Build]
and type in the command build number
253
, select
[Label]
and enter a label of up to 40 characters in
length, select either
[Display]
to display the label on the panel when the command build
253
is triggered.
Configure the Command build action:
Press
Menu On/Off
button and select
[SetUp]
->
[Usercode]#
, momentarily press
<etc>
to select
[SetUp]
->
[Build]
and type in the command build number
253
, select
[Action]
->
[Start MA]
->
[Enter]
->
[Reversbl]
and
[Enter]
.
Commissioning instructions
42
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
Vigilon
C
ompact
Panel
Power
CB253
CB254
Sounder
Pre mid 2015
Power
Sounder
Active
Fault/Dis
Fire Routing O/P
Post mid 2015