Checking device STATUS
Loop Device Status
To list the STATUS of a device on an allocated loop at the Control Panel: Press
Menu On/Off
button and then select
[Info]
, momentarily press
<etc>
to select [
Status]
->
[Device],
enter the
device number, select
[Loop]
, enter the loop number n on which the device resides, select
[Enter]
to view device status information.
Analogue Channel 1 is forward scatter optical smoke sensor
Analogue Channel 2 is heat sensor
Analogue Channel 3 is for CO gas sensor
Analogue Channel 4 is for backward scatter optical smoke sensor
Analogue Channel 5 reports sounder/flasher/speech faults to the control panel
Analogue Channel 6 reports monitored input/monitored output faults to the control panel
O - Output, I - Input and . signify - not used
Device
digital I / O
channels
S4 Dual OH/Red VAD
O . . O
1, 2, 4, 5
S4 Heat/Voice Sen Sndr/Red VAD
OOOO
2, 5
S4 Dual OH/Voice Sen Sndr/Red VAD
. OOO
1, 2, 4, 5
S4 Dual OH/CO/Voice Sen Sndr/Red VAD
OOOO
1, 2, 3, 4, 5
S4 Dual OH/White VAD
O . . O
1, 2, 4, 5
S4 Dual OH/White VAD (HP)
O . . O
1, 2, 4, 5
S4 Dual OH/Voice Sndr/White VAD (Std)
OOOO
1, 2, 4, 5
S4 Dual OH/Voice Sen Sndr/White VAD (HP)
OOOO
1, 2, 4, 5
S4 Heat/Voice Sndr/White VAD (HP)
OOOO
2, 5
S4 Dual OH CO/Voice Sen Sndr / White VAD (HP)
OOOO
1, 2, 3, 4, 5
S4 Dual OH/Voice Sounder
. OOO
1, 2, 4, 5
S4 OH Sensor Sounder
. OOO
1, 2, 5
S4 Dual OH Sensor Sounder
. OOO
1, 2, 4, 5
S4 Heat Sensor Sounder
. OOO
2, 5
S4 Dual OH CO Sensor
. . . O
1, 2, 3, 4, 5
S4 Heat Sensor
. . . O
2
S4 Heat Sensor Sounder
. OOO
2, 5
S4 Dual Optical Heat Sensor
. . . O
1, 2, 4
S4 Dual Optical Heat Sensor CO
. . . O
1, 2, 3, 4, 5
S4 Dual Optical Heat Sensor Sounder
. OOO
1, 2, 4, 5
+ Monitored input
6
+ Monitored output
6
Other devices
Beam transmitter
. . . O
2
Beam receiver
. . . O
1- raw data
2- average
data
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
65
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Checking
device
STATUS
Loop 1 No.
7 Dual optical/Heat/CO
LB1:C
End1:Hi
End2:Hi
I/O:...0 Anal:1-4
2nd:250 3rd:0 Short delay:0
Zone 1
Zone 1
LED)
,6
Loop on which
the device is installed
Location of the
device on the loop
Device description
Monitored Input / LED is
attached to the device
Loop breaker
condition
C:closed
Status of End 1
of the device
(high or low)
Status of End 2
of the device
(high or low)
Digital
Input outputs
Analogue channels
used
1:Optical (forward)
2:Heat
3:Gas
4:Optical (Backward)
5:Sounder/VAD (Strobe)/Speech fault
6:Monitored line or LED
Secondary address
denotes group of devices
Tertiary address
used primarily by
sounders/VAD (strobe)
Short circuit delay
associated with
number of T breakers
off T breakers
Zone number and label