Device
digital I / O
channels
MCP
. . . O
6
Repeat panel
. . . O
-
Zonal mimic
. . . O
-
Mimic panel
. . . O
-
T-breaker
. . . O
Loop interface
all possible
I - input
O - output
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5
Interface unit (mains powered)
all possible
I - input
O - output
1-channel 1
2-channel 2
3-channel 3
4-channel 4
5-battery
6-mains
S cubed
OOOO
1 - IR control
2 - Tone
3 - Power
4 - VAD
(Strobe)
5
Device
digital I / O
channels
The legacy products below are for reference
S-Quad Dual Optical Heat Sensor Strobe
O . . O
1, 2, 4, 5
S-Quad Dual Optical Heat Sensor Sounder
. OOO
1, 2, 4, 5
S-Quad Dual Optical Heat Sensor Speech Strobe OOOO
1, 2, 4, 5
S-Quad Dual Optical Heat Sensor CO Speech
Strobe
OOOO
1, 2, 3, 4, 5
Slave LED
. . . O +L
Sounder
. OO .
3 - Low freq.
2 - On/Off
Repeat sounder
. OO .
Optical
. . . O
1
Optical heat
. . . O
1,2
Heat
. . . O
4
Slave Relay
O . . O+R
Single channel interface unit
I O . O
1,2,5
Loop powered zone module
I . . O
1,5
Optical/Heat Sounder
. OOO
1,2
"
The correct device type may not be displayed if the loop circuit has allocation faults.
¨
Check that the device is of the correct type and is suitable for the area in which it is
installed.
¨
Check the digital status of all devices.
¨
On successful allocation
check that the total number of devices found equals the
number installed
. Also note there will be a loop voltage on the unconnected end of the
cable.
Commissioning instructions
66
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
Checking
device
STATUS