Single network without domain bridge
Powering-up the Network
¨
Add one panel at a time starting from the
network controller,
adding one panel/node
at a time to
side 1
.
"
It can take a few minutes for the system map to update.
¨
For each panel powered-up the
network controller
will automatically try to establish
communication with the connected equipment.
¨
The
network controller
will display the status of the network as being started, secure
or non-secure and from now on will monitor and control the network
communications.
¨
Use
disable comms
to isolate a panel from the rest of the network, ie it operates at the
network card in an echo mode, select
Menu On/Off
->
[Control] -> [Disable] ->
[Comms]
and enter the Network Card address, usually card 6.
How to check a Network map
¨
Using the
Menu On/Off
->
[Info] -> [Map] -> [NetMap]
menu, enter the network
card address, usually card 6 and select
[E]
.
The display will provide a list in cabling order the addresses of panels/nodes in the
networked system.
Here are examples of different networks. The lowest address ‘1’ is normally the
network controller.
Nodes on side 1 of a SECURE NETWORK
1
10
4
24
3
6
2
22
7
23
1
Nodes on side 1 of a NON-SECURE NETWORK
1
10
4
24
3
6
Nodes on side 2 of NON-SECURE NETWORK
1
23
7
22
2
4188-856_issue 7_07/15_Generic Vigilon (C VA) Comms.
91
Vigilon 4/6 loops & Compact (VA) panels & network nodes
Single
V
igilon
N
etwork
must all be set to the same
settings at all the panels / nodes in a single
networked system without domain bridge.
IO Card switches must be set to the Off
position. The network baud and domain
address switch are located on the DKC.
These switches
Node 1
Node 3
Node 2
Control panel
Network Card
Address 2
Baud 38.4K
Control panel
Network Card
Address 4
Baud 38.4K
Control panel
Network
Card
Address
1
Baud
38.4K
Control panel
IO
Card
all
switches
to
Of
f
position
Network
Card
Address
3
Baud
38.4K
Node 4
DKC
Address
1
Baud
19.2K
IO
Card
all
switches
to
Of
f
position
IO Card
all switches to
Off position
DKC
Address 1
Baud 19.2K
DKC
Address 1
Baud 19.2K
IO Card
all switches to
Off position
DKC
Address
1
Baud
19.2K