Section 3 - Installing the Control
2-5
Single-Partition Single-Panel Mode
To access the Single-Partition, Single Panel mode, perform the following steps:
Step Action
1
Enter
User Code (for users 001-050)
+
[#]
+
[86].
2
Enter the panel ID number
(01-08)
of the panel you want to link to.
3
Enter the partition number of the panel. The keypad displays “AWAITING PANEL LINK.” After a few
seconds, the keypad displays the status of the partition along with the panel ID number and partition
number flashing in the upper right-hand corner. The user now has full control of the remote control panel.
All functions can be performed except the following:
•
Those limited by the user’s authority level.
•
The user cannot enter Installer Program mode.
•
The user cannot execute another panel linking mode.
NOTE:
To execute another panel linking mode or to access a different remote panel, the user must first
exit this mode (return to the original control panel).
4
To exit, enter the
User Code (for users 001-050)
+
[#]
+
[85].
After a few seconds, the keypad displays
the status of the original partition for the keypad.
Multi-Partition Multi-Panel Mode
To perform a function in the Multi-Partition, Multi Panel mode, follow the steps below:
Step Action
1
Enter
User Code (for users 001-050)
+
[#]
+
[88].
The keypad displays the following:
PANELnn 1 2 3 4 5 6 7 8
STATUS
x x x x x x x x
where “nn” = panel ID number (01-08), “12345678” are the partition numbers and “xxxxxxxx” is the status
of each partition of that panel. Status indications include:
A
= Armed Away
S
= Armed Stay
M
= Armed Maximum
I
= Armed Instant
R
= Ready
N
= Not Ready
B
= Bypassed/Ready
✴
= Alarm
T
= Trouble
F
= Fire Alarm
P
= AC Power Failure
L
= Low System Battery
C
= Comm Fail
NOTES:
See table later in this section for priority of displays.
A
“
•
” under a partition number indicates the user does NOT have access to that partition.
2
The following functions can be performed:
Press
[1]
to attempt to disarm all partitions.
Press
[2]
to attempt to arm AWAY all partitions.
Press
[3]
to attempt to arm STAY all partitions.
Press
[4]
to attempt to arm MAXIMUM all partitions.
Press
[7]
to attempt to arm INSTANT all partitions.
Press
[
✴
]
to read the status of the next panel.
Press
[#]
key to read the status of the previous panel.
Press
[0]
to exit mode. After a few seconds, the keypad displays the status of the original partition of the
original panel for the keypad. Also, this mode will end in approximately 120 seconds if no keys are pressed.
NOTES:
When performing any of the arming commands, if there are faults in any of the partitions, none of
the partitions will arm. These faults must be corrected or bypassed before attempting to arm.
When performing either a STAY or INSTANT arm command the system always arms in mode 1.
The user cannot execute another panel linking mode. To execute another panel linking mode or to
access a different remote panel, the user must first exit this mode (return to the original control
panel).
WWW.DIYALARMFORUM.COM