VISTA-128BP/VISTA-250BP Installation and Setup Guide
4-6
ZONE #
1st
2nd
ZONE #
1st
2nd
ZONE #
1st
2nd
ZONE #
1st
2nd
209
14 00
227
02 00
244
04 00
ALARM RST.
00 00
210
15 00
228
03 00
245
05 00
TROUBLE
00 00
211
01 00
229
04 00
246
06 00
TRBLE. RST
00 00
212
02 00
230
05 00
247
07 00
BYPASS
00 00
213
03 00
231
06 00
248
08 00
BYP. RST.
00 00
214
04 00
Zone Response Type Definitions
Each zone must be assigned a zone type, which defines
the way in which the system responds to faults in that
zone. There are three keypad-activated zones (panic
keys; see note) for each partition, a polling loop
supervision zone, and four RF supervisory zones, two
for each RF receiver installed. Zone types are defined
below.
Type 00: Zone Not Used
Program with this zone type if the zone is not used.
Type 01: Entry/Exit #1 Burglary
Provides entry delay whenever the zone is faulted and
the system is armed in the AWAY or STAY mode.
When the panel is armed in the INSTANT or
MAXIMUM mode, no entry delay is provided. Exit
delay begins whenever the control is armed, regardless
of the arming mode selected. These delays are
programmable.
Assign this zone type to zones that are used for
primary entry to and exit from the facility.
Type 02: Entry/Exit #2 Burglary
Provides a secondary entry delay, if the system is
armed in the AWAY or STAY modes and the zone is
faulted. When the panel is armed in the INSTANT or
MAXIMUM mode, no entry delay is provided.
Secondary exit delay begins whenever the control is
armed, regardless of the arming mode selected. These
delays are programmable.
Assign this zone type to zones that are used for entry
and exit of the facility and require more time than the
primary entry and exit point. Delay times for this
zone type must be greater than those for zone type 01
(e.g., a garage, loading dock, or basement door).
Type 03: Perimeter Burglary
Provides an instant alarm if the zone is faulted and
the system is armed in the AWAY, STAY, INSTANT,
or MAXIMUM mode.
Assign this zone type to all exterior door and window
zones.
Type 04: Interior, Follower
Provides a delayed alarm (using the programmed entry
delay time) if an entry/exit zone is faulted first.
Otherwise it produces an instant alarm. It is active
when the system is armed in the AWAY or MAXIMUM
mode, but the MAXIMUM mode eliminates the entry
delay.
If the Interior Follower zone is programmed for one of
the STAY modes (default is STAY mode 1), it is
automatically bypassed when the panel is armed in the
STAY or INSTANT mode.
Assign this zone type to a zone covering an area such
as a foyer, lobby, or hallway through which one must
pass upon entry or exit (to and from the keypad).
Type 05: Trouble by Day/Alarm by Night
Provides an instant alarm if the zone is faulted and
the system is armed in the AWAY, STAY, INSTANT,
or MAXIMUM mode. During the disarmed state (day),
the system annunciates a latched trouble sounding
from the keypad (and a central station report, if
desired).
Assign this zone type to a zone that contains a foil-
protected door or window (such as in a store), or to a
zone covering a sensitive area such as a stock room or
drug supply room. It can also be used on a zone in an
area where immediate notification of an entry is
desired.
Type 06: 24-Hour Silent Alarm
Sends a report to the central station but provides no
keypad display or sounding. Assign this zone type to a
zone containing an Emergency button.
Type 07: 24-Hour Audible Alarm
Sends a report to the central station and provides an
alarm sound at the keypad and an audible external
alarm. Assign this zone type to a zone containing an
Emergency button.
Type 08: 24-Hour Auxiliary Alarm
Sends a report to central station and provides an
alarm sound at the keypad only.
(No bell output is
provided.)
Assign this zone type to a zone an
Emergency button or one containing monitoring
devices such as water sensors or temperature sensors.
Type 09: Supervised Fire (Without Verification)
Provides a fire alarm on a short circuit and a trouble
condition on open circuit. A fire alarm produces a
pulsing of the bell output. A zone of this type is always
active and cannot be bypassed.