Section 4 – Programming
4-7
Type 10: Interior with Delay
Provides entry and exit delays (using the programmed
entry and exit delay times) when armed in the AWAY
mode. Provides only exit delay when armed in the
MAXIMUM mode (no entry delay).
If the Interior with Delay zone is programmed for one
of the STAY modes (default is STAY mode 1), it is
automatically bypassed when the panel is armed in the
STAY or INSTANT mode. Delay begins whenever
sensors in this zone are violated, regardless of whether
or not an entry/exit delay zone was tripped first.
Assign this zone type to a zone covering an area such
as a foyer, lobby, or hallway through which one must
pass upon entry or exit (to and from the keypad).
Type 14: PLM Supervision
Provides supervision of remote Panel Link Modules. If
the communication between the local PLM and a
remote PLM fails, a trouble message is produced for
the PLM zone.
Type 16: Fire With Verification
Provides a fire alarm on a short circuit and a trouble
condition on open circuit. An initial short detection
causes 7-second smoke detector power reset. A
subsequent short detection within 90 seconds of the
reset causes a fire alarm. A fire alarm produces a
pulsing of the bell output. A zone of this type is always
active and cannot be bypassed.
Type 20: Arm-STAY
(
5800 Series devices only)
Causes the system to arm in the STAY mode when the
zone is activated.
Type 21: Arm-AWAY
(
5800 Series devices only)
Causes the system to arm in the AWAY mode when
the zone is activated.
Type 22: Disarm
(
5800 Series devices only)
Causes the system to disarm when the zone is
activated.
Type 23: No Alarm Response
Used on a zone when an output relay action is desired,
but with no accompanying alarm (e.g., for lobby door
access).
Type 27: Access Point
Assign this zone type to an input device (hardwired
zone, wireless zone, keypad, access control relay, etc.)
that controls an access entry point (e.g., a door). The
access point entry relay can be assigned to an access
control relay (controlled by the VISTA-128BP/VISTA-
250BP), ECP relay (4204), or to the access control
system independent of the control panel.
Type 28: Main Logic Board (MLB) Supervision
Used to supervise the MLB. If communication between
the MLB and the VISTA Gateway Module (VGM) fails,
a trouble condition is annunciated for the zone. Also,
if the communication fails, all access control system
(ACS) input zones also display a “CHECK.”
Type 29: Momentary Exit
Used to cause an access point programmed for entry to
revert to an exit point for 15 seconds. After the 15
seconds, it automatically reverts back to an entry
point. This zone type should be used only with
VistaKey modules.
NOTE FOR PANIC KEYS:
Keypad panic zones share the same
zone response type for all 8 partitions, but panics may be
individually enabled for each partition.
IMPORTANT! FAULT ANNUNCIATION
Polling loop and RF troubles (zones 988, 990, and 997) report as
trouble conditions only, and as such, should be assigned zone type
05 if annunciation is desired. See
Polling Loop Supervision
and
RF
System Operation and Supervision
in
SECTION 3 Installing the
Control
for more information.
Zone Input Type Definitions
Each zone must be assigned an input type, which
defines the where the system will “look” for status of
the zone (RF receiver, polling loop, etc.). Zone input
types are defined below.
Type 01 Hardwired (HW)
Reserved for the built-in hardwired zones 1-9.
Type 02 RF Motion (RM)
Select for 5800 Series RF transmitters. Sends periodic
check-in signals, as well as fault and low-battery
signals. The control panel automatically restores the
zone to “ready” after a few seconds. This type is
designed for facilities with multiple motion detectors
that may fault and restore simultaneously. The
transmitter must remain within the receiver’s range.
NOTE:
If using RF Motion with a door/window type
transmitter, only loop 1 may be used.
Type 03 Supervised RF (RF)
Select for 5800 Series RF transmitters that will be
supervised for check-in signals. The transmitter must
remain within the receiver’s range.
Type 04 Unsupervised RF (UR)
Select for 5800 Series RF transmitters that will not be
supervised for check-in signals. The transmitter may
therefore be carried off-premises.
Type 05 Unsupervised Button RF (BR)
Select for 5800 Series RF transmitters specifically
designed for this input type. Check the transmitter’s
instructions for proper programming of the input type.
These transmitters send only fault signals. They do
not send low-battery signals until they are activated.
The transmitter may be carried off-premises.
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM