background image

VR8245 AND VR8345 UNIVERSAL ELECTRONIC IGNITION GAS CONTROLS

9

69-2013

Check And Adjust Gas Input to Main 

Burner

CAUTION

Fire or explosion hazard.

1. Do not exceed the input rating stamped on the 

appliance nameplate, or manufacturer 
recommended burner orifice pressure for the 
size orifice(s) used. Make certain the primary 
air supply to the main burner is properly 
adjusted for complete combustion (refer to the 
appliance manufacturer instructions).

2. WHEN CHECKING GAS INPUT BY 

CLOCKING THE GAS METER:
• Make sure that the only gas flow through the 

meter is that of the appliance being checked.

• Make certain that other appliances are turned 

off with pilot burners extinguished (or deduct 
that gas consumption from the meter 
reading).

• Convert the flow rate to Btuh as described in 

Gas Controls Handbook, form 70-2602, and 
compare to the Btuh input rating on the 
appliance nameplate.

3. WHEN CHECKING GAS INPUT WITH A 

MANOMETER (PRESSURE GAUGE):
• To connect the manometer, be sure the gas 

control knob is in the OFF position before 
removing the outlet pressure tap plug.

• When removing the manometer, turn the gas 

control knob back to OFF and replace the 
outlet pressure tap plug.

• Shut off the gas supply at the appliance 

service valve, or at the gas tank for LP gas, 
before removing the outlet pressure tap plug 
and before disconnecting the manometer and 
replacing the outlet pressure tap plug.

• Perform the Gas Leak Test at the outlet 

pressure tap plug.

Standard-Opening Pressure Regulator

1.

The gas control outlet pressure should match the 
manifold pressure listed on the appliance name-
plate.

2.

With the main burner operating, check the gas con-
trol flow rate by using the meter clocking method or 
check the gas pressure using a manometer con-
nected to the gas control outlet pressure tap. See 
Fig. 3.

3.

If necessary, adjust the pressure regulator to match 
the appliance rating. Refer to Table 6 for the factory 
set nominal outlet pressures and adjustment setting 
ranges.
a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw clockwise 

 to increase or counter-

clockwise 

 to decrease the main burner gas 

pressure.

c. Always replace the cap screw and tighten firmly 

to safeguard proper operation.

4.

If the desired outlet gas pressure or gas flow rate 
cannot be achieved by adjusting the gas control, 
check the gas control inlet pressure by using a 
manometer at the inlet pressure tap. If the inlet 
pressure is in the normal range (refer to Table 6 and 
7), replace the gas control. Otherwise, take the nec-
essary steps to provide proper gas pressure to the 
gas control.

Standard and Slow-Opening (H and M) Models

1.

Carefully check the main burner lightoff. Make sure 
that the main burner lights smoothly and that all 
ports remain lit.

2.

Check the full rate manifold pressure listed on the 
appliance nameplate. Gas control full rate outlet 
pressure should match this rating.

3.

With main burner operating, check the control flow 
rate using the meter clocking method or check pres-
sure using a manometer connected to the outlet 
pressure tap on the control. See Fig. 3.

4.

If necessary, adjust the pressure regulator to match 
the appliance rating. See Table 6 and 7 for factory-
set nominal outlet pressure and adjustment range.
a. Remove the pressure regulator adjustment cap 

screw.

b. Using a screwdriver, turn the inner adjustment 

screw (Fig. 3) clockwise 

 to increase or 

counterclockwise 

 to decrease the gas pres-

sure to the burner.

c. Always replace the cap screw and tighten firmly 

to prevent gas leakage.

5.

If the desired outlet pressure or flow rate cannot be 
achieved by adjusting the gas control, check the 
gas control inlet pressure using a manometer at the 
inlet pressure tap of the gas control. If the inlet pres-
sure is in the nominal range (see Table 6 and 7), 
replace the gas control. Otherwise, take the neces-
sary steps to provide proper gas pressure to the 
control.

Two-Stage (Q) Models 

Two-stage models require that you check and adjust both 
high and low pressure regulator settings. Two-stage 
appliance operating sequences vary. Consult the 
appliance manufacturer instructions for the specific 
operating sequence and regulator adjustment procedure 
for the appliance in which the control is installed.

1.

Set appliance to operate on high.

2.

Carefully check the main burner lightoff. Make sure 
that the main burner lights smoothly and that all 
ports remain lit.

3.

Check the full rate (high) manifold pressure listed 
on the appliance nameplate for high pressure. The 
gas control full rate outlet pressure should match 
this rating.

4.

With main burner operating, check the gas control 
flow rate using the meter clocking method or check 
pressure using a manometer connected to the out-
let pressure tap on the gas control. See Fig. 3.

5.

If necessary, adjust the high pressure regulator to 
match the appliance rating. See Table 6 and 7 for 
factory-set nominal outlet pressure and adjustment 
range.
a. Remove the pressure regulator adjustment cap 

(Fig. 3).

b. Using a screwdriver, turn the inner adjustment 

screw for HI pressure clockwise 

 to increase 

or counterclockwise 

 to decrease the gas 

pressure to the burner.

6.

After high pressure has been checked, check low 
pressure regulation. Two-stage appliance operat-
ing sequences vary. Consult the appliance manu-
facturers instructions for the specific operating 
sequence and regulator adjustment procedure for 
the appliance in which the control is installed and 
for instructions on how to prevent the control from 
moving to high stage while checking the low pres-
sure regulator setting.

Summary of Contents for VR8245

Page 1: ...e conversion factors in Table 2 to convert capacities for other gases APPROVALS American Gas Association Design Certificate L2025007 Canadian Gas Association Design Certificate L2025007 PIPE ADAPTERS Includes two 3 4 to 1 2 inch NPT bushings and one 1 2 to 3 8 inch NPT bushing CROSS REFERENCE See Table 4 for cross reference information INSTALLATION WHEN INSTALLING THIS PRODUCT 1 Read these instruc...

Page 2: ...ressure Regulator Type Current Draw A Conversion Kits Natural Gas LP LP Natural Gas VR8245M 1 2 x 1 2 Standard 5 393691 394588 VR8345H 3 4 x 3 4 Slow Opening 7 393691 394588 VR8345M 3 4 x 3 4 Standard 7 393691 394588 VR8345Q 3 4 x 3 4 2 Stage 9 396021 396025 Table 4 Cross Reference Universal Replacement Cross Reference Universal Service Part Honeywell White Rodgers Robert Shaw VR8245M2530 VR8204A1...

Page 3: ... over gas control inlet or outlet 2 Apply moderate amount of good quality pipe com pound to bushing leaving two end threads bare See Fig 1 3 Insert bushing in gas control and carefully thread pipe into the bushing until tight Fig 1 Use moderate amount of pipe compound Location Locate the combination gas control in the appliance vestibule on the gas manifold In replacement applications locate the g...

Page 4: ...diment trap 4 Apply a moderate amount of good quality pipe com pound do not use Teflon tape to pipe only leaving two end threads bare See Fig 1 On LP installa tions use compound resistant to LP gas 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to gas control inlet and outlet Use wrench on the square ends of the gas control See Fig 3 and 4 When working with an intermi...

Page 5: ...de a gas tight seal 5 Push tubing into the pilot gas tapping on the outlet end of the control until it bottoms While holding tub ing all the way in slide compression fitting into place engage threads and turn until finger tight Then tighten one more turn with wrench Do not overtighten Refer to Fig 5 and 6 6 Connect other end of tubing to pilot burner accord ing to pilot burner manufacturer instruc...

Page 6: ... Connect control circuit to gas control terminals See Fig 3 and 8 9 or 10 4 Adjust the thermostat heat anticipator to 0 7 the rat ing stamped on the valve operator Fig 7 Install wire adapter for hot surface or direct spark ignition systems Pilot plug must be in the valve pilot opening Fig 8 VR8245M VR8345M H wiring connections in intermittent ignition system M8440A PV M V PV M V OFF ON PILOT GAS S...

Page 7: ... 0 2 VALVE LOAD 120VAC HOT 570A0056 WARNING Explosion hazard Can cause serious injury or death This device can malfunction if it gets wet Never try to use a device that has been wet replace it GND BURNER 24V GND VALVE GND 24V LED L2 HSI HSI L1 SENSE VALVE MPLS MN 55422 SEE INSTRUCTIONS FOR REMOTE SENSE DUAL ROD APPLICATIONS TRIAL TIME NUM OF TRIALS CONFIGURATION PLUG 120VAC NEUTRAL TRIAL TIME 7 SE...

Page 8: ...er solution anytime work is done on a gas control Gas Leak Test 1 Paint all pipe connections upstream of the gas con trol with a rich soap and water solution Bubbles indicate a gas leak 2 If a gas leak is detected tighten the pipe connection CAUTION Fire or explosion hazard Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flashback in the appli...

Page 9: ... burner lightoff Make sure that the main burner lights smoothly and that all ports remain lit 2 Check the full rate manifold pressure listed on the appliance nameplate Gas control full rate outlet pressure should match this rating 3 With main burner operating check the control flow rate using the meter clocking method or check pres sure using a manometer connected to the outlet pressure tap on the...

Page 10: ...e to the safety shutdown or safety lockout tests recommended for the intermittent pilot IP hot surface HSI or direct spark DSI module When different use the procedure rec ommended for the module 1 Turn off gas supply 2 Set the thermostat or controller above room temperature to call for heat 3 Intermittent Pilot Ignition Watch for an igni tion spark at pilot burner either immediately or following p...

Page 11: ...s that are used seasonally should be checked before shutdown and again before the next use Consequence of unexpected shutdown Where the cost of an unexpected shutdown would be high the system should be checked more often Dusty wet or corrosive environment Since these environments can cause the gas control to deteriorate more rapidly the system should be checked more often NOTE If the gas control w...

Page 12: ...ge tampering bent terminals missing or broken parts stripped threads or evidence of exposure to heat IMPORTANT Follow the operating instructions provided by the manufacturer of your heating appliance The information below will be of assistance in a typi cal gas control application but the specific con trols used and the procedures outlined by the manufacturer or your appliance may differ and requi...

Reviews: