background image

9

69-0624—2

Service

WARNING

FIRE OR EXPLOSION HAZARD CAN
CAUSE PROPERTY DAMAGE, SEVERE
INJURY OR DEATH
Do not disassemble the gas control; it contains no
replaceable components. Attempted disassembly
or repair may damage the gas control.

CAUTION

Do not apply a jumper across or short the valve coil
terminals. Doing so can burn out the heat anticipa-
tor in the thermostat.

IMPORTANT: Allow 60 seconds after shutdown before re-

energizing step-opening model to assure lightoff at
step pressure.

IF THE PILOT BURNER FLAME WILL NOT
LIGHT

1. Assure the main gas supply valve is open and the pilot

gas supply line is purged of air.

2. Attempt to light pilot burner flame following proce-

dures in the Lighting the Pilot Burner Flame section. If pilot
burner flame still will not light:

a. Check the pilot gas adjustment screw. If closed, read-

just the pilot flame. Refer to Adjust the Pilot Burner
Flame section.

b. Perform the Gas Leak Test at the compression fitting.

If a gas leak is detected, replace the old compression
fitting or tighten the newly installed one. Refer to Fig. 4.

c. Assure that the pilot burner tubing or pilot burner

orifice is not clogged.

IF THE PILOT BURNER FLAME GOES OUT
WHEN THE GAS CONTROL KNOB IS RELEASED

1. Assure the gas control knob is held in at least one

minute to allow the thermocouple time to heat.

2. Check the pilot burner flame adjustment. Refer to

Adjust the Pilot Burner Flame section.

3. Check the wiring between the thermocouple and the

gas control valve operator.

4. Assure thermocouple connection to the power unit is

tightened one-fourth turn beyond finger tight.

5. If pilot burner flame still goes out, measure the open

and closed thermocouple output voltage. Compare it to the
acceptable range charts in the thermocouple specifications
or in the Gas Controls Handbook. Replace the thermocouple
if voltages are outside the acceptable range.

6. Check the power unit resistance. If above 11 ohms,

replace the gas control.

IF THE MAIN BURNER WILL NOT COME ON
WITH A CALL FOR HEAT

1. Be sure the gas control knob is in the ON position.
2. Adjust the thermostat several degrees above room

temperature.

3. Use an ac voltmeter to measure the voltage across

terminals TH and TR or MV/PV and MV. If:

a. No voltage is present, check the control circuit for

proper operation.

b. 24 Vac is present, but first operator did not click open,

check for excessive inlet gas pressure. If inlet gas
pressure is correct, replace the gas control.

4. Measure the open and closed thermocouple output

voltages and compare to the acceptable range charts in the
thermocouple specifications or in the Gas Controls Hand-
book. Replace the thermocouple if voltages are outside the
acceptable range.

5. Measure the open and closed thermocouple output

voltages and compare to the acceptable range charts in the
thermocouple specifications or in the Gas Controls Hand-
book. Replace the thermocouple if voltages are outside the
acceptable range.

IF THE MAIN BURNER IS OVERFIRING

Adjust the gas control pressure regulator to the correct

pressure. If the regulator cannot be adjusted and supply the
pressure is in the normal range, replace the gas control.

INSTRUCTIONS TO THE HOMEOWNER

CAUTION

FIRE OR EXPLOSION HAZARD CAN
CAUSE PROPERTY DAMAGE, SEVERE
INJURY, OR DEATH
Follow these warnings exactly:
1. Pilot burner flame must be lit manually. Follow

these instructions exactly.

2. Before lighting pilot burner flame, smell around

the appliance for gas. Be sure to smell next to
floor because LP gas is heavier than air.

3. IF YOU SMELL GAS:

• Turn off the gas supply at the appliance

service valve. On LP gas systems, turn off
the gas supply at the gas tank.

• Do not light any appliances in the house.
• Do not touch electrical switches or use the

phone.

• Leave the building and use a neighbor’s

phone to call your gas supplier.

• If you cannot reach your gas supplier, call

the fire department.

4. Do not force the gas control knob. Use only

your hand to push down or turn the gas control
knob. Never use any tools. If the gas control
knob will not operate by hand, the gas control
should be replaced by a qualified service tech-
nician. Force or attempted repair can result in a
fire or explosion.

5. Replace the gas control in case of any physical

damage, tampering, bent terminals, missing or
broken parts, stripped threads, evidence of ex-
posure to heat or if flooded by water.

Summary of Contents for VR8300

Page 1: ... cu m hr 290 cu ft hr 8 2 cu m hr 3 4 x 3 4 200 cu ft hr 5 7 cu m hr 30 cu ft hr 0 8 cu m hr 300 cu ft hr 8 5 cu m hr a Capacity based on 1000 Btu cu ft 0 64 specific gravity natural gas at 1 in wc pressure drop 37 3 MJ cu m 0 64 specific gravity natural gas at 0 25 kPa pressure drop Model Number Ambient Temperature Range Regulator Type VR8300A 0 F to 175 F 18 C to 79 C Standard opening VR8300C 0 ...

Page 2: ...use a gas control set for natural gas on LP gas or a gas control set for LP gas on natural gas ToconvertagascontrolfromnaturalgastoLPgasorfrom LP gas to natural gas contact your Honeywell representative Standard orslow openinggascontrolsareconvertedfrom one gas to another with a conversion kit ordered separately Order part number 393691 to convert from natural to LP gas Order part number 394588 to...

Page 3: ...ontrol 0 90 degrees in any direction from the upright position of the gas control knob 2 Mount the gas control so gas flow is in the direction of the arrow on the bottom of the gas control 3 ThreadpipetheamountshowninTable5forinsertion into gas control IMPORTANT Donotthreadpipetoofar Valvedistortion or malfunction may result if the pipe is inserted too deeply into the gas control Refer to Fig 3 TA...

Page 4: ...INLET PRESSURE TAP PRESSURE REGULATOR ADJUSTMENT UNDER CAP SCREW PILOT OUTLET PILOT ADJUSTMENT UNDER CAP SCREW GAS CONTROL KNOB RED RESET BUTTON M1639C GAS CONTROL TIGHTEN NUT ONE TURN BEYOND FINGER TIGHT FITTING BREAKS OFF AND CLINCHES TUBING AS NUT IS TIGHTENED TO BURNER M3076A provided on the gas control Never use the old compres sion fitting because it may not provide a gas tight seal 4 Push t...

Page 5: ...NCE TERMINALS TH TR TH TR VR8300 TERMINALS HIGH LIMIT CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED DO NOT JUMPER THESE TERMINALS THIS SHORTS VALVE COIL AND MAY BURN OUT ANTICIPATOR IN THERMOSTAT CONVENIENCE TERMINALS SERVE AS A TIE POINT ONLY THEY ARE NOT INTERNALLY WIRED TO THE CONTROL CIRCUIT OR TO GROUND OPTIONAL HIGH LIMIT 1 2 3 4 2 3 4 M8581 Fig 9 VR830...

Page 6: ...n a gas control GAS LEAK TEST 1 Paint all pipe connections upstream of the gas control with a rich soap and water solution Bubbles indicate a gas leak 2 If a gas leak is detected tighten the pipe connection CAUTION Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flashback in the appliance vestibule 3 Light the main burner 4 With the main burne...

Page 7: ...Using a screwdriver turn the inner adjustment screw clockwise to increase or counterclockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to be sure of proper operation 4 If the desired outlet gas pressure or gas flow rate cannot be achieved by adjusting the gas control check the gas control inlet pressure using a manometer at the inlet pressure tap I...

Page 8: ...l system The maintenance program should include regular check out of the gas control as outlined in Start up and Checkout section checkout the control system as described in the appliance manufacturers literature Maintenance frequency must be determined individually for each application Some considerations are Cyclingfrequency Appliancesthatmay cycle100 000 times annually should be checked monthly...

Page 9: ...ostat several degrees above room temperature 3 Use an ac voltmeter to measure the voltage across terminals TH and TR or MV PV and MV If a No voltage is present check the control circuit for proper operation b 24 Vac is present but first operator did not click open check for excessive inlet gas pressure If inlet gas pressure is correct replace the gas control 4 Measure the open and closed thermocou...

Page 10: ...gas continue with the next step 6 Remove the pilot burner access panel located below and behind the gas control 7 Find the pilot burner by following the metal tube from the gas control The pilot burner is located between the two burner tubes behind the pilot burner access panel 8 Turn the gas control knob counterclockwise to PILOT 9 Push and hold the gas control knob all the way in Immediately lig...

Reviews: