background image

VR9105V, F AND VR9205V, F DIRECT IGNITION GAS CONTROL WITH INTEGRATED 1:1 REGULATOR

69-2471EF—01

2

Fig. 1. VR9105V, F and VR9205V, F End Outlet.

Fig. 2. VR9105V, F and VR9205V, F Side Outlet.

PLANNING THE 
INSTALLATION

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury, 
or death.

Follow these warnings exactly:

1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in 

the Maintenance section.

Heavy demands are made on the controls when direct 
ignition systems are used on central heating equipment in 
barns, greenhouses, and commercial properties and on 
heating appliances such as commercial cookers, 
agricultural equipment, industrial heating equipment and 
pool heaters.

Special steps may be required to prevent nuisance 
shutdowns and control failure due to frequent cycling, 
severe environmental conditions related to moisture, 
corrosive chemicals, dust or excessive heat. These 
applications require Honeywell Combustion Engineering 
review; contact your Honeywell Sales Representative for 
assistance.

Review the following conditions that can apply to your 
specific installation and follow the precautions suggested.

M32193

2-11/16 (65)

1-1/16

(27)

1/8

(3)

1-3/16

(30)

1-3/16

(30)

1:1 REGULATOR

OUTLET

PRESSURE

TAP 1/6-27 

NPT

REFERENCE

PRESSURE

CONNECTION

OUTLET

1/2-14 

NPT

3-3/16

(80)

5 (127)

INLET

1/2-14

NPT

3/8 (9)

INLET PRESSURE 

TAP 1/6-27 NPT

3-7/16

(87)

7/8 (22)

M32194

OUTLET

PRESSURE

TAP 1/6-27 

NPT

REFERENCE

PRESSURE

CONNECTION

1-3/16

(30)

2-11/16 (65)

1-1/16

(27)

1-3/16

(30)

1/8

(3)

3-3/16

(80)

OUTLET 1/2-14 NPT

5 (127)

3-3/16 (80)

INLET

1/2-14

NPT

3-7/16

(87)

3/8 (9)

INLET 

PRESSURE 

TAP 1/6-27 NPT

7/8 (22)

1:1 REGULATOR

Summary of Contents for VR9105F

Page 1: ...uctions 69 2484EF Valve capacities are shown in Table 1 For suffix letter designation see Table 2 a Capacity based on 1000 Btu ft3 0 64 sp gr natural gas at 1 in wc pressure drop 37 3 MJ m3 0 64 sp gr natural gas at 0 25 kPa pressure drop b Minimum and Maximum regulation is at the max fire Minimum regulation at low fire is 18 KBtu h at 0 7 in WC outlet pressure a For detailed information about Ven...

Page 2: ...cial steps may be required to prevent nuisance shutdowns and control failure due to frequent cycling severe environmental conditions related to moisture corrosive chemicals dust or excessive heat These applications require Honeywell Combustion Engineering review contact your Honeywell Sales Representative for assistance Review the following conditions that can apply to your specific installation a...

Page 3: ... shielding should be provided by the appliance manufacturer verify proper air circulation is maintained when the appliance is installed INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for y...

Page 4: ...to Control All piping must comply with local codes and ordinances or with the National Fuel Gas Code ANSI Z223 1 NFPA No 54 whichever applies Tubing installation must comply with approved standards and practices 1 Use new properly reamed pipe that is free from chips If tubing is used make sure the ends are square deburred and clean All tubing bends must be smooth and without deformation 2 Run pipe...

Page 5: ...former and other controls as required 3 Connect the control circuit to the gas control terminals 4 Ensure combustion chamber is free of gas before startup 5 Adjust thermostat heat anticipator to the rating stamped on valve operator Electrical Connection VR9105V F and VR9205V F can be connected to any standard direct ignition control with 110 Vac output by using rectifier plug 45900441 039 or 24 Va...

Page 6: ...er than to the appliance being checked Other appliances must remain off with the pilots extinguished or deduct their consumption from the meter reading Convert flow rate to Btuh as described in form 70 2602 Gas Controls Handbook and compare to Btuh input rating on appliance nameplate 3 IF CHECKING GAS INPUT WITH MANOME TER Make sure the plug is not connected to the coil connector before removing o...

Page 7: ...one complete cycle to make sure all controls operate properly MAINTENANCE Under normal circumstances no maintenance or service is required WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not disassemble the gas control it contains no replaceable components Attempted disassembly repair or cleaning can damage the control resulting in gas leakage SERVICE WARNING F...

Page 8: ...formation below describes a typical control application but the specific controls used and the procedures outlined in your appliance manufacturer instructions can differ requiring special instructions To Turn ON Appliance STOP Read the Warnings Above Before Proceeding 1 The lighting sequence on this appliance is automatic do not attempt to manually light the main burner 2 If the appliance does not...

Page 9: ...sont illustrées dans le Tableau 1 Pour le suffixe de référence consulter le Tableau 2 a Capacité basée sur 1000 Btu pied3 gravité spécifique de 0 64 gaz naturel chute de pression de 1 po c e 37 3 MJ m3 gravité spécifique 0 64 gaz naturel et chute de pression de 0 25 kPa b Régulation minimum et maximum à combustion maximum La régulation minimum à basse combustion est de 18 KBtu h à une pression de ...

Page 10: ...pes spéciales sont requises pour éviter les coupures intempestives et les pannes de régulateur dues à des mises en marche et arrêts fréquents des conditions environnementales rigoureuses liées à l humidité des produits chimiques corrosifs de la poussière et une chaleur excessive Ces applications nécessitent d être révisées par le département d ingénierie de la combustion de Honeywell contacter le ...

Page 11: ...ante maximum autour du régulateur ne dépasse pas les conditions de température de fonctionnement du régulateur Si l appareil fonctionne à de très hautes températures utiliser un isolant une protection et assurer une circulation d air adéquate pour protéger le régulateur Une isolation ou une protection adéquate doit être fournie par le fabricant de l appareil vérifier qu une circulation d air adéqu...

Page 12: ...n ventilée Monter le régulateur suffisamment haut au dessus du bas de l armoire pour éviter l exposition à des déversements ou des éclaboussures d eau Veiller à ce que la température ambiante ne dépasse pas les valeurs de température ambiante nominales pour chaque organe Couvrir le régulateur à gaz si l appareil est nettoyé à l eau à la vapeur ou avec des produits chimiques et pour éviter l accumu...

Page 13: ...structions générales ci dessous Si ces instructions diffèrent de celles du fabricant de l appareil suivre celles du fabricant RÉGULATEUR À GAZ RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU ALIMENTATION EN GAZ TUYAU 76 MM 3 PO MINIMUM 76 MM 3 PO MINIMUM COLONNE MONTANTE RÉGULATEUR À GAZ HORIZONTAL COLONNE DESCENDANTE 76 MM 3 PO MINIMUM COLONNE M...

Page 14: ...pourraient causer un retour de flamme dans le vestibule de l appareil 4 Avec le brûleur principal allumé appliquer une solution savonneuse épaisse sur les joints du tuyau y compris les douilles et l entrée et la sortie du régulateur 5 Si une autre fuite est détectée éteindre le régulateur à gaz et serrer les joints et les raccords du tuyau 6 Remplacer la pièce si la fuite ne peut pas être réparée ...

Page 15: ... allumeur à incandescence immédiatement ou suite au prébalayage Voir les spécifications du module d allumage direct 4 Minuter la durée de l étincelle Voir les spécifications du module d allumage direct 5 Après le verrouillage du module connecter l obturateur au connecteur de serpentin et s assurer qu il n y a pas de débit de gaz vers le brûleur principal 6 Régler le thermostat à une température in...

Page 16: ... chauffage Les informations ci dessous décrivent une application typique mais les régulateurs spécifiques utilisés et les procédures décrites dans les instructions du fabricant de l appareil peuvent différer nécessitant des instructions spéciales Pour mettre l appareil en marche STOP Lire les avertissements ci dessus avant de continuer 1 La séquence d allumage de cet appareil est automatique ne pa...

Reviews: