Programming Function Blocks and Features
Video Recorder – User Manual
88
Table 4-6 Standard Algorithm Prompts
(continued)
Prompt
Range/Selections
Definition
TEMPERATURE UNIT
Select C for Degrees Celsius, F for
Degrees Fahrenheit, K for Kelvin, R for
Rankine, or NONE.
Specifies the temperature units used for
thermocouple, pyrometer, and RTD input
types. The default setting is F. If you change
the default, be sure to change the analog
input’s RANGE LOW and RANGE HIGH
values accordingly. The instrument will not
adjust these values by itself.
Ignore the TEMPERATURE UNIT prompt or
set it to NONE, if the analog input being
programmed will not be used for temperature
measurements.
DIRECT/INDIRECT
Select DIRECT for thermocouple,
pyrometer, or RTD inputs. Select INDIR
(Indirect) for volt or millivolt signal inputs
from linear or non-linear transmitters.
Select SQRT (Square Root) for extracting
flow measurements from a voltage input
representing differential pressure
measurements. If SQRT is chosen, the
RANGE LOW and RANGE HIGH must be
adjusted to specify the upper and lower
limits of the flow units span.
Note that the term “direct” generally applies to
input types where the sensors in direct
physical contact with the monitored process
are also in direct physical contact with the
instrument terminal board. The term “indirect”
applies to inputs from transmitters since the
sensors in direct physical contact with the
monitored process are indirectly connected to
the instrument through the transmitter circuitry
and wiring.
CIRCUIT LOW
OFF or number
Appears only if “INDIR” or “SQRT” was
previously selected. Is the actual low end
value of voltage to be used for Indirect
measurements.
CIRCUIT HIGH
OFF or number
Appears only if “INDIR” or “SQRT” was
previously selected. Is the actual high end
value of voltage to be used for Indirect
measurements.
ELECTRICAL UNITS
Select whether the CIRCUIT LOW or
CIRCUIT HIGH values specified are in
units of VOLTS, MV (millivolts), or OHMS.
Circuit low and circuit high units.
LAG
≥
0 seconds or OFF
“LAG” is a time constant applied to the input
measurement value. This provides digital
filtering (LAG) to the measurement.
Lag appears on menu only if EXPANDED
INPUT is enabled under Enable Features in
the Program menu.
SAMPLE HOLD
OFF, discrete parameter, 0, 1
Holds Input. The input value is measured
normally when this discrete is OFF and holds
its last value when the discrete is ON(1).
Hold appears on menu only if EXPANDED
INPUT is enabled under Enable Features in
the Program menu.
FAILSAFE
For thermocouples only, Upscale (UP),
Downscale (DOWN) or None.
Determines whether or not failsafe is active
and, if so, which direction.
CLAMPING
HI RANGE clamps the input at the
RANGE HIGH value. LO RANGE clamps
input at the RANGE LOW value. RANGE
clamps input over both the low and high
range values. NONE gives no clamping.
Clamps input at specified value.
ATTENTION
: Clamping is not recommended
for process variable inputs to control loops.
Summary of Contents for VRX180
Page 1: ...Issue 3 03 03 US1I 6228 Video Recorder VRX180 User Manual ...
Page 2: ...Issue 3 03 03 US1I 6228 ...
Page 6: ...iv Video Recorder User Manual ...
Page 48: ...Installation Video Recorder User Manual 34 ...
Page 222: ...Setpoint Profiler Video Recorder User Manual 208 ...
Page 234: ...Online Operations Using Primary Displays Video Recorder User Manual 220 ...
Page 278: ...Appendix A Video Recorder User Manual 264 ...