W8735G COMMUNICATION GATEWAY

7

69-2432—01

Fig. 12. Wiring the AUX-OUT Terminal Block to a Home 

Security Panel.

NOTE: For the wiring in Fig. 12, be sure to check the exact 

connections with the Home Security Panel Installa-

tion Instructions-Auxiliary Devices.

Fig. 13. Wiring the AUX-OUT Terminal Block to Line 

Voltage Annunciating Device (Buzzer).

Phone/Network Communication

The W8735G Communication Gateway can update the 

Application server using either a dial-up or broadband 

connection. See Fig. 14. When the W8735G detects an alarm 

condition, it queues up the alarm report to the server. If the 

alarm message is active on the bus for a period exceeding 5 

minutes, the gateway connects to the server and delivers its 

alarm report. If the gateway fails to connect while attempting 

to deliver an alarm report, it will retry at five minute intervals 

until successful.

The W8735G also reports a runtime data log for the bus or 

busses it is monitoring. During a 24 hour period, a W8735G 

communicating via a phone connection will dial out once 

between midnight and 4:00 

AM

 local time to deliver the 

previous day's log. Broadband gateways update the server 

every 30 minutes. Applications requiring closer monitoring 

and faster updates should be connected to a network 

connection.

Upon power-up, the gateway will conduct a self test which 

includes a broadband or dial-up attempt using a pre-

programmed 800 number. Dial-up connections are only used 

in cases where Broadband connections are unavailable. For 

best performance, connect to both Network and Telephone 

connections. See Fig. 14.

Fig. 14. Connecting the gateway to a network or phone 

line.

IMPORTANT

— A phone line filter will be required if the gateway is 

sharing the line with a DSL modem.

— The gateway will not attempt to dial out if the tele-

phone line is in use.

— Use only with analog telephone lines.

IMPORTANT

If the phone line is needed while the gateway is con-

nected, simply picking up a phone off the hook will 

cause the gateway to release the line. Other 

instances/phone systems may require pressing the 

Flash button on the telephone.

HOME SECURITY 

PANEL

AUXILIARY

CHANNEL 1

CHANNEL 2

OUTPUT

INPUT

AUXILIARY

M23757

1/D 
2/R 
3/B

1/D 
2/R 
3/B

CHANNEL 1

CHANNEL 2

OUTPUT

INPUT

AUXILIARY

L1
L2

N.O. 24 VAC

RELAY

24 VAC

TRANSFORMER

BUZZER

1/D 
2/R 
3/B

1/D 
2/R 
3/B

M23758

W8735G

COMMUNICATION 

GATEWAY

ENVIRACOM

BUS

M29954

1/D

2/R

3/B

TELEPHONE

POWER

NETWORK

TELEPHONE

JACK

CABLE/DSL MODEM

ROUTER

EnviraCOM™

Enabled      

Status

Summary of Contents for W8735G

Page 1: ...duct 2 Installer must be a trained experienced service techni cian 3 Complete all wiring connections to the gateway before powering up the 24Vac system transformer and plug ging in the gateway power supply into an outlet 4 All wiring must comply with applicable local electrical codes ordinances and regulations INSTALLATION Mount the W8735G in the equipment room near the indoor HVAC equipment Posit...

Page 2: ...allasts and large distribution pan els Failure to follow these wiring practices may intro duce electrical interference noise which can cause erratic system operation All unused wire is to be grounded at controller end only The bus wire to ter minal 1 D must not exceed 1 000 feet 305 M General Wiring Directions Refer to Fig 3 and Table 1 for the location and function of each terminal IMPORTANT Wire...

Page 3: ...ary Output DO Connect to N O contact alarm input Auxiliary Output DO Connect to N O contact alarm input Auxiliary Input DI Connect to N C sensor contact 18 30 Vac Vdc Auxiliary Input DI Connect to N C sensor contact 18 30 Vac Vdc Channel 3 Model 1018 only 1 D channel 3 To EnviraCOM channel 3 network DATA 2 R channel 3 To EnviraCOM channel 3 network 24 Vac Hot 3 B channel 3 To EnviraCOM channel 3 n...

Page 4: ...MMUNICATION GATEWAY TO OPTIONAL ENVIRACOM CONTROLS AND SENSORS M29961 1 D 2 R 3 B THERMOSTAT OPTIONAL REVIEW COMPONENTS AND ACCESSORIES SECTION FOR COMPATIBLE DEVICES 1 VISIONPRO IAQ 2 2 1 TELEPHONE POWER NETWORK 1 2 3 R7184U OIL PRIMARY CONTROL Status Event Priority Description LED Color Flashes Battery good LOWEST Normal Operation Green Solid Battery low Replace the battery Green Off Battery dea...

Page 5: ...se NOTE The Auxiliary Output is made on all alert conditions and is deactivated when the alert is cleared from the communication bus IMPORTANT Make sure the current draw through the Auxiliary Output terminals does not exceed specifications Use relays or contactors to integrate to line voltage devices Fig 6 AUX IN and AUX OUT Terminals located on the main circuit board Auxiliary Input and Output Ap...

Page 6: ...HANNEL 2 OUTPUT INPUT AUXILIARY POWER FROM THE AUXILIARY INPUT SUPPLIED BY TRANSFORMER 1 T87 OR SIMILAR 1 M23753 1 D 2 R 3 B 1 D 2 R 3 B COMBINATION OF DEVICES CONNECTED IN SERIES TO ANNUNCIATE ON ANY EVENT ON THE AUX IN LOOP 1 CHANNEL 1 CHANNEL 2 OUTPUT INPUT AUXILIARY 1 M23754 1 D 2 R 3 B 1 D 2 R 3 B N C N C COMBINATION OF DEVICES CONNECTED IN PARALLEL TO ANNUNCIATE ON AN AND EVENT ON THE AUX IN...

Page 7: ...ate the server every 30 minutes Applications requiring closer monitoring and faster updates should be connected to a network connection Upon power up the gateway will conduct a self test which includes a broadband or dial up attempt using a pre programmed 800 number Dial up connections are only used in cases where Broadband connections are unavailable For best performance connect to both Network a...

Page 8: ...his routine is repeated between midnight and 4 00 AM local time at which point dial out attempts cease The routine is repeated during the next reporting time of midnight 4 00 AM IMPORTANT For best gateway performance connect to both the network and phone Gateway Updates Periodically the gateway may require a firmware upgrade to enable new features supported by the web application This will occur a...