Table 6. DIP Switches 3 - 10.
DIP Switch
Function
On (Up, Default)
Off (Down)
3
Type of furnace
Conventional/non-communicating
EnviraCom Communicating
4
Purge time
Two minutes
3.5 minutes
5
Fan control during purge
HVAC controlled
Panel controlled
6
Damper control during
purge
Last zone(s) calling open during purge
Open all dampers during purge
7
Heat pump compressor
stages
One stage
Two stages
8
Fan control in heat
Fan controlled by panel in cool and
HVAC equipment in heat
Fan controlled by panel in heat and
cool
9
Heat pump changeover
O (Cool changeover)
B (heat changeover)
10
Not used
—
—