background image

4

W884B,E

INSTALLATION

Installation

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to fol-

low them could damage the product or cause a hazard-
ous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

CAUTION

1. Disconnect power supply before beginning

installation to prevent electrical shock or
equipment damage.

2. On gas systems, turn off gas before starting

installation.

LOCATION

Locate the W884 about 5 ft [1.5 m] above the floor in

an area with good air circulation at average temperature.

Do not mount the W884 where it may be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall

behind the thermostat.

MOUNTING

IMPORTANT: The thermostat used with the W884 was

mounted at true level when calibrated at the fac-
tory. The W884 must be level to maintain calibra-
tion.

1. Remove cover and thermostat and level W884 at

the selected location. Mark locations for mounting screws
and wiring access hole. See Fig. 2.

2. Drill a 1/2 to 3/4 in. [13 to 19 mm] hole for the

wires, and small pilot holes for the mounting screws.

3. Run cable and auxiliary wires (if used) to location.

Pull in the required number of wires. All wiring is 24V.

4. Carefully slip the thermostat wires through the

hole in the subbase, and insert humidistat and auxiliary
wires (if used) through the square wiring hole on the side
of the subbase platform. See Figs. 3 and 4.

Fig. 2—Level the W884 and then mark the
position of mounting holes with a pencil.

!

Fig. 3—Thermostat wires are brought through
the hole on the subbase; wires for the humi-
distat are brought through the hole on the side
of the subbase platform.

Summary of Contents for W884B

Page 1: ... The W884E includes a dehumidifier control All comfort controls are combined in the W884 to make a convenient attractive control center CONTENTS Specifications 2 Ordering Information 2 Recycling Notice 3 Installation 4 Settings and Adjustments 7 Checkout 9 Humidistat dial on the W884B can be set for prevailing outdoor temperature to provide opti mum relative humidity over a wide range of con ditio...

Page 2: ... outdoor temperature W884E The dial is marked ON LOW NOR MAL HIGH and OFF Optimum relative hu midity is maintained by rotating the humidity selection dial DIFFERENTIAL 4 to 6 percent RH cycling at midscale THERMOSTAT RATINGS Switching Spdt Switch Rating 1 5A at 30 Vac Range 50 F to 100 F 10 C to 38 C Adjustable Heat Anticipator Range 0 10 to 1 2A factory set at 0 4A SUBBASE RATINGS System Switch C...

Page 3: ... at the end of its useful life If this control is replacing a control that contains mer cury in a sealed tube do not place your old control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 ...

Page 4: ...ant heat from the sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat MOUNTING IMPORTANT The thermostat used with the W884 was mounted at true level when calibrated at the fac tory The W884 must be level to maintain calibra tion 1 Remove cover and thermostat and level W884 at the selected location Mark locations for mounting screws a...

Page 5: ...ion Push excess wire back into wall and plug the hole to prevent drafts from affect ing the W884 7 Mount the thermostat and replace W884 cover WIRING Disconnect power supply to prevent electrical shock or equipment damage All wiring must comply with local codes and ordi nances Wiring to the W884 must be NEC Class 2 Humidistat requires separate 24V power supply Refer to the wiring diagrams and inst...

Page 6: ...AY W B G Y O H H Q539 DEHUMIDISTAT W884E 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USED IN DUCT HEATER OR SIMILAR APPLICATIONS TO ENERGIZE SYSTEM FAN DURING HEATING M1335 FAN RELAY 2 2 SPST N C SWITCHING RELAY R 1 HUMIDIFIER RELAY COOLING DAMPER MOTOR COOLING CONTACTOR FAN RELAY HEATING RELAY W B G Y O H H Q539A HUMIDISTAT W884B 1 POWER SUPPLY PROVIDE DISCONNECT M...

Page 7: ...et as recom mended and frost or condensation forms on inside windows adjust humidistat setting for outdoor tem per ature setting less 5 F 3 C Frost or condensa tion should disappear within 24 hours If not con tinue reducing outdoor temperature setting and ad just humidistat accordingly Humidity Selection W884B The humidity controller should be set at the prevail ing outdoor temperature This will p...

Page 8: ... rating of the primary control this rating is usually stamped on the control nameplate Move the indicator on the scale to correspond with this rating and the heat anticipator will be properly adjusted Move the indicator with your fin gers a pin a pencil point or a wire inserted in the small hole See Fig 11 If the current rating is not given proceed as follows before mounting the thermostat 1 Conne...

Page 9: ... system through one complete cycle to make sure all components function as intended CAUTION On low voltage gas system if jumpering gas valve to check system operation do NOT jumper across valve coil This may burn out thermostat heat anticipator See Fig 12 Fig 12 Do not jumper across valve coil ...

Page 10: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: