background image

7

60-2289—6

W884B,E

INSTALLATION  •  SETTINGS AND ADJUSTMENTS

Fig. 9—W884E with separate heating and cooling, dehumidifier relay coil, heating damper motor.

R

1

DEHUMIDIFIER
RELAY

HEATING 
RELAY OR 
VALVE

COOLING 
CONTACTOR

FAN 
RELAY

HEATING 
DAMPER 
MOTOR

W

B

G

Y

O

H

H

Q539

DEHUMIDISTAT

W884E

1 POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 

PROTECTION AS REQUIRED.

M1331

Settings and Adjustments

TEMPERATURE SELECTION

To select the temperature control point, turn the trans-

parent dial until the pointer is in line with the desired
point on the setting (top) scale.

HUMIDITY SELECTION

IMPORTANT: If the humidistat is set too high during

cold weather, condensation on windows may occur.
This indicates there is too much moisture in the air,
which could lead to structural damage if allowed to
persist. Set the humidistat at the recommended
setting shown below. If humidistat is set as recom-
mended and frost or condensation forms on inside
windows, adjust humidistat setting for outdoor tem-
per-ature setting less 5

°

F [3

°

C]. Frost or condensa-

tion should disappear within 24 hours. If not, con-
tinue reducing outdoor temperature setting and ad-
just humidistat accordingly.

Humidity Selection W884B

The humidity controller should be set at the prevail-

ing outdoor temperature. This will provide optimum
relative humidity control for most installations.

TABLE 1—

RECOMMENDED RELATIVE HUMIDITY LEVEL.

Outdoor Temperature

(Degrees F)

+20

Type Of

and

Construction

-20

-10

0

+10 Above

Double Glass

15% 20% 25% 30%

35%

Single Glass

10% 15% 20% 25%

30%

Single Glass

20% 25% 30% 35%

40%

with Storm Window

Humidity Selection W884E

The humidity selection dial can be set to any position

between ON and OFF. The HIGH position is approxi-
mately 70 percent relative humidity; normal is approxi-
mately 50 percent RH, and LOW is approximately
30 percent RH.

NOTE: For dehumidification in cooling, the W884E

should be wired in parallel for independent control of
temperature and relative humidity.

Summary of Contents for W884B

Page 1: ... The W884E includes a dehumidifier control All comfort controls are combined in the W884 to make a convenient attractive control center CONTENTS Specifications 2 Ordering Information 2 Recycling Notice 3 Installation 4 Settings and Adjustments 7 Checkout 9 Humidistat dial on the W884B can be set for prevailing outdoor temperature to provide opti mum relative humidity over a wide range of con ditio...

Page 2: ... outdoor temperature W884E The dial is marked ON LOW NOR MAL HIGH and OFF Optimum relative hu midity is maintained by rotating the humidity selection dial DIFFERENTIAL 4 to 6 percent RH cycling at midscale THERMOSTAT RATINGS Switching Spdt Switch Rating 1 5A at 30 Vac Range 50 F to 100 F 10 C to 38 C Adjustable Heat Anticipator Range 0 10 to 1 2A factory set at 0 4A SUBBASE RATINGS System Switch C...

Page 3: ... at the end of its useful life If this control is replacing a control that contains mer cury in a sealed tube do not place your old control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 ...

Page 4: ...ant heat from the sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat MOUNTING IMPORTANT The thermostat used with the W884 was mounted at true level when calibrated at the fac tory The W884 must be level to maintain calibra tion 1 Remove cover and thermostat and level W884 at the selected location Mark locations for mounting screws a...

Page 5: ...ion Push excess wire back into wall and plug the hole to prevent drafts from affect ing the W884 7 Mount the thermostat and replace W884 cover WIRING Disconnect power supply to prevent electrical shock or equipment damage All wiring must comply with local codes and ordi nances Wiring to the W884 must be NEC Class 2 Humidistat requires separate 24V power supply Refer to the wiring diagrams and inst...

Page 6: ...AY W B G Y O H H Q539 DEHUMIDISTAT W884E 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED USED IN DUCT HEATER OR SIMILAR APPLICATIONS TO ENERGIZE SYSTEM FAN DURING HEATING M1335 FAN RELAY 2 2 SPST N C SWITCHING RELAY R 1 HUMIDIFIER RELAY COOLING DAMPER MOTOR COOLING CONTACTOR FAN RELAY HEATING RELAY W B G Y O H H Q539A HUMIDISTAT W884B 1 POWER SUPPLY PROVIDE DISCONNECT M...

Page 7: ...et as recom mended and frost or condensation forms on inside windows adjust humidistat setting for outdoor tem per ature setting less 5 F 3 C Frost or condensa tion should disappear within 24 hours If not con tinue reducing outdoor temperature setting and ad just humidistat accordingly Humidity Selection W884B The humidity controller should be set at the prevail ing outdoor temperature This will p...

Page 8: ... rating of the primary control this rating is usually stamped on the control nameplate Move the indicator on the scale to correspond with this rating and the heat anticipator will be properly adjusted Move the indicator with your fin gers a pin a pencil point or a wire inserted in the small hole See Fig 11 If the current rating is not given proceed as follows before mounting the thermostat 1 Conne...

Page 9: ... system through one complete cycle to make sure all components function as intended CAUTION On low voltage gas system if jumpering gas valve to check system operation do NOT jumper across valve coil This may burn out thermostat heat anticipator See Fig 12 Fig 12 Do not jumper across valve coil ...

Page 10: ...ome and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A QUALITY IS KEY ...

Reviews: