WEB/CP-202-XPR AND WEB/CP-602-XPR CONTROLLERS
95-7775—01
20
For both local and remote I/O, each input or output used requires a special Niagara
AX
Remote Input/Output (Nrio) point to be
added in the station database. These components act as the station interface to the physical I/O points. The Nrio points you need
for each input or output type are noted in previous wiring sections in
boldface
.
For Nrio software details, see the
NiagaraAX NRIO Guide
in Workbench online Help, or the same document in PDF.
COMMUNICATIONS WIRING
Communications ports on the controller are alongside the edge of the controller board, accessible with the right cover removed
(Fig. 15). Communications port types include
Ethernet
and
Serial
.
NOTE: Prior to connecting cables, provide strain relief for them to prevent damage to the controller.
Fig. 15. Controller communications ports and other connectors.
Ethernet
Two, female 10/100 Mbps Ethernet connections are provided on the controller. These are RJ-45 connectors labeled
PRI
and
SEC
. Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch.
The controller’s factory-default IP address for
PRI
(NET1) is
192.168.1.12
n
, where the last numeral
n
in the address
matches the last digit in the controllers’s serial number, and the subnet mask is
255.255.255.0
.
By default, SEC (NET2) on the unit is disabled.
Refer to the
JACE NiagaraAX Install and Startup Guide
for details on changing IP address.
NOTE: Typically, you
only use PRI
(primary port), unless you have a specific application for isolating a driver’s network traffic to
a separate LAN, using SEC. Do
not
use SEC as the primary port.
Serial
There are two “RS” serial ports on the controller’s base board. Each has a UART capable of operation up to 115,200 baud.
• An RS-232 port uses an RJ-45 socket connector, and operates as COM1.
• An isolated RS-485 port is on three terminals of a 6-position screw-terminal connector, and operates as COM2 (by default).
M28877
RIGHT SIDE
COVER
REMOVED
RS-485
COM2
RS-232
(RJ-45)
COM1
OPTION SLOT
CONNECTOR AREA
(SEE ABOUT
OPTION CARDS
ON PAGE 12)
SEC
SECONDARY
ETHERNET
(RJ-45)
USB PORT
WEB/CP-602-XPR
ONLY
(FUTURE USE)
UNIVERSAL
INPUTS
(8 TOTAL)
PRI
PRIMARY
ETHERNET
(RJ-45)
EXTERNAL 12V
BACKUP BATTERY
12V + P BATT. OUT (PB)
15V PS + OUT (PB+)
15V PS - OUT (PB-)
RELAY
OUTPUTS (4)
ANALOG
OUTPUTS (4)
EARTH GROUND
TERMINALS (10)