WEB/CP-202-XPR AND WEB/CP-602-XPR CONTROLLERS
29
95-7775—01
Non-replaceable Parts
Fuse
The controller contains a non-user replaceable fuse, soldered on the main circuit board. This fuse provides protection from
internal shorts or connection to incorrect power supplies. If the fuse circuitry is suspect, contact your regional Tridium office for
technical support. See
Returning a Defective Unit
on page 31.
Standard Replacement Parts
Standard replacement parts are listed in Table 4 and can be ordered from stock without restriction. Standard replacement parts
cannot be returned for credit and should be disposed of in an appropriate manner.
New Replacement Unit
To replace an entire unit, order and install a
new
WEB/CP-202-XPR or WEB/CP-602-XPR. If the faulty controller is
still in
warranty
, you may receive credit by returning it to Tridium. Contact Tridium for a return authorization (RMA) number before
shipping any item for return credit. See
Returning a Defective Unit
on page 31, for more details.
NOTE: Before ordering a new replacement unit, it is strongly recommended that you contact your normal technical support
resource to eliminate the possibility of a software issue or mis-configuration problem.
REPLACING THE WEB/CP-202-XPR OR WEB/CP-602-XPR CONTROLLER
WARNING
Before replacing, power to the controller must be OFF, and all LEDs out! In addition, power must be removed to
any I/O devices wired back to the controller. Failure to do so may result in electrical shock or equipment damage.
CAUTION
Before handling circuit boards, discharge any accumulated static by touching a nearby grounded object. For
details, see “Static Discharge Precautions” section on page 6.
To replace a controller with a new replacement unit, proceed as follows:
Replacing a controller.
1.
If possible, use the appropriate Niagara
AX
software tool to back up the controller’s configuration to your PC.
2.
Disconnect power to the controller, including the disconnection of an external 12V battery, if used. The unit should power
down automatically. Wait for all LEDs to remain off.
3.
Disconnect all power to any I/O devices wired to the controller.
Table 4. Standard Replacement Parts for WEB/CP-202-XPR or WEB/CP-602-XPR.
Part Number
Description
H11393
NiMH Battery Pack Assembly; see
Replacing the NiMH Battery
on page 27.
H11364
Hardware Bag for WEB/CP-202-XPR or WEB/CP-602-XPR containing removable screw terminal
connector blocks (two 7-position, three 6-position, one 2-position).
H11166
Replacement right-angle GSM/GPRS quad-band SMA coax-mounted stub antenna.
H-GPRS-CBL-EXT 6.56 feet (2m) SMA-type coax extension cable with mounting bracket. See Fig. 2 on page 7.
H10148
Adapter; RJ-45 to DB-9 null modem for onboard RS-232 serial port to connect to DTE device.
H10180
Silver satin patch cable; 4 feet (used between adapter and serial port).
H10181
Silver satin patch cable; 10 feet (used between adapter and serial port).
H10182
Silver satin patch cable; 25 feet (used between adapter and serial port).
712BNP