WEBVISION™
95-7769—01
130
RO LED
nvoHydStatus
rOLed
EnumPoint
HYD Status Mode
nvoHydStatus
mode
EnumPoint
Alarm Type
nvoHydStatus
alarmType
EnumPoint
DLC Shed
nvoHydStatus
dlcShed
NumericPoint
Effective Window Open
nvoHydStatus
effWindowOpen
NumericPoint
HW Window Open
nvoHydStatus
hwWindowOpen
NumericPoint
Fan Feedback
nvoHydStatus
fanFeedback
NumericPoint
External Active
nvoHydStatus
externalActive
NumericPoint
Fan Stages Active
nvoHydStatus
fanStagesActive
EnumPoint
Output Position 0
nvoHydStatus
outputPosition0
NumericPoint
Output Position 1
nvoHydStatus
outputPosition1
NumericPoint
Reheat Active
nvoHydStatus
reheatActive
EnumPoint
Effective Setpoint
nvoHydStatus
activeSetPt
NumericPoint
Space Temperature
nvoHydStatus
spaceTemp
NumericPoint
Reset Bypass Time
nvoHydStatus
restBypassTime
NumericPoint
Terminal Load
nvoTerminalLoad
levPercent
NumericPoint
Manual Mode
nviManualMode
ManualMode
EnumPoint
Table 80. HYD Point Details. (Continued)
Point Name
Network Variable
Field Name
Point Type
Table 81. HYD Application of Points.
Point name
Graphics Alarms Trends Commandable Internal Use
Valid Values
Occupied Cool (SetPoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Cool (SetPoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Cool (SetPoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Occupied Heat (SetPoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (SetPoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (SetPoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State
X
Default
Occupied
Unoccupied
Bypass
Standby