Excel 10 Remote Input/Output
Device (RIO)
Table 82 provides the RIO points detail and Table 83 on
page 136 provides the RIO application of points.
Table 82. RIO Point Details.
Point name
Network Variable
Field
Point Type
Communication Failed
nvoAlarmStatus
CommFail
EnumPoint
Node Disabled
nvoAlarmStatus
NodeDisable
EnumPoint
Sensor Failed
nvoAlarmStatus
SensorFail
EnumPoint
Manual Mode
nviManualMode
manMode
EnumWritable
Analog In 1
nvorioIO
ai1
NumericPoint
Analog In 2
nvorioIO
ai2
NumericPoint
Analog In 3
nvorioIO
ai3
NumericPoint
Analog In 4
nvorioIO
ai4
NumericPoint
Analog In 5
nvorioIO
ai5
NumericPoint
Analog In 6
nvorioIO
ai6
NumericPoint
Digital In 1
nvorioIO
di1
EnumPoint
Digital In 2
nvorioIO
di2
EnumPoint
Digital In 3
nvorioIO
di3
EnumPoint
Digital In 4
nvorioIO
di4
EnumPoint
Digital Out 1
nvorioIO
d01
EnumPoint
Digital Out 2
nvorioIO
d02
EnumPoint
Digital Out 3
nvorioIO
d03
EnumPoint
Digital Out 4
nvorioIO
d04
EnumPoint
Digital Out 5
nvorioIO
d05
EnumPoint
Digital Out 6
nvorioIO
d06
EnumPoint
Digital Out 7
nvorioIO
d07
EnumPoint
Digital Out 8
nvorioIO
d08
EnumPoint
Mode
nvorioIO
mode
EnumPoint
Table 83. RIO Application of Points.
Point Name
Graphics
Alarms
Trends
Commandable
Internal Use
Valid Values
Communication Failed
X
False or True
Node Disabled
X
False or True
Sensor Failed
X
False or True
Manual Mode
X
X
X
X
Enable
Disable
Manual
Suppress Alarms
Unsuppress Alarms
Analog In 1
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Analog In 2
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0