Occupied Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Standby Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Unoccupied Heat (Setpoint)
X
Units=ºC
Precision=2
Min=10.0
Max=35.0
Current State
X
ocOccupied
ocUnoccupied
ocBypass
ocStandby
ocNul
Next State
X
ocOccupied
ocUnoccupied
ocBypass
ocStandby
ocNul
Time To Next State
X
Units=min
Precision=0
Min=0.0
Max=65535.0
DLC Shed
X
dlNoDlcShed
dlMinDlcShed
Air Flow Loss
X
false or true
Communication Failed
X
false or true
Dirty Filter
X
false or true
Drip Pan Full
X
false or true
Freeze State
X
false or true
Frost Protect
X
false or true
Indoor Air Quality Override
X
false or true
Invalid Setpoint
X
false or true
Low Limit Economizer Close
X
false or true
Node Disabled
X
false or true
Outside Air Quality
X
false or true
Sensor Failed
X
false or true
Table 85. UV Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values