WEBVISION™
95-7769—01
142
Cool Position
X
X
X
Units=%
Precision=0
Min=-128.0
Max=127.0
Cool Stages On
X
X
X
Units=null
Precision=0
Min=0.0
Max=3.0
DLC Shed
X
X
X
Restored or Shed
Dirty Filter
X
X
X
False or True
Discharge Air Setpoint
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Discharge Air Temperature
X
X
X
Units=ºF
Precision=1
Min=-256.0
Max=256.0
Drip Pan Full
X
X
X
False or True
Economizer Enabled
X
X
X
Default
Off
Low
Medium
High
On
Economizer Float Synch
X
X
X
Off or On
Economizer Position
X
X
X
Units=%
Precision=0
Min=-128.0
Max=127.0
Effective Occupancy
X
X
X
Default
Occupied
Unoccupied
Bypass
Standby
Fan Speed
X
X
X
Units=null
Precision=0
Min=0.0
Max=7.0
Fan Switch
X
X
X
Default
Off
Low
Medium
High
On
Filter Pressure
X
X
X
Units=in/wc
Precision=1
Min=-32.0
Max=32.0
Free State 1
X
X
X
Off or On
Heat Percent
X
X
X
Units=%
Precision=1
Min=-163.8
Max=163.8
Table 85. UV Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values