WEBVISION™
95-7769—01
152
Vacon NX Frequency Converter
(NXVFD)
Table 88 provides the NXVFD points detail and Table 89 on
page 153 provides the NXVFD application of points.
Table 88. NXVFD Point Details.
Point Name
Network Variable
Field Name
Point Type
Application Type
nciApplVer
applicationType
NumericWritable
Application Version
nciApplVer
versionNo
NumericWritable
Application Ver Time
nciApplVer
time
NumericWritable
Device Name
nciDeviceName
DeviceName
String Writable
Adjust Input
nviProcessIn3
levPercent
NumericWritable
Free Analog Input
nviProcessIn2
levPercent
NumericWritable
Torque Reference
nviProcessIn1
levPercent
NumericWritable
Adjust Input / Actual Value 2
nviProcessIn3
levPercent
NumericWritable
Clear Counter
nviClrCntr
value
NumericWritable
Drive Speed Setpoint
nviDrvSpeedStpt
value
NumericWritable
Free Analog / Input Actual Value 1
nviProcessIn2
levPercent
NumericWritable
Reset Fault
nviRstFault
value
NumericWritable
Torque Reference / Reference for PID
nviProcessIn1
levPercent
NumericWritable
AC Fault Code
nvoProcessOut8
levPercent
NumericPoint
Fault Active
nvoDrvStatus
bit3
BooleanPoint
DC Link Voltage
nvoProcessOut7
levPercent
NumericPoint
Drive Current
nvoDrvCurnt
amp
NumericPoint
Drive Energy
nvoDrvEnrgy
elecKwh
NumericPoint
Drive Power
nvoDrvPwr
powerKilo
NumericPoint
Ready
nvoDrvStatus
bit0
BooleanPoint
Running
nvoDrvStatus
bit1
BooleanPoint
Drive Speed
nvoDrvSpeed
levPercent
NumericPoint
Active Fault Code
nvoActFault
count
NumericPoint
Motor Current
nvoProcessOut3
levPercent
NumericPoint
Motor Power
nvoProcessOut5
levPercent
NumericPoint
Motor Speed
nvoProcessOut2
levPercent
NumericPoint
Motor Torque
nvoProcessOut4
levPercent
NumericPoint
Motor Voltage
nvoProcessOut6
levPercent
NumericPoint
Output Frequency
nvoProcessOut1
levPercent
NumericPoint
Reference Eq Actual
nvoDrvStatus
bit5
BooleanPoint
Drive Run Hours
nvoDrvRunHours
timeHour
NumericPoint
Counter Clockwise
nvoDrvStatus
bit2
BooleanPoint
Warning Active
nvoDrvStatus
bit4
BooleanPoint