WEBVISION™
95-7769—01
170
Unoccupied Heat (Setpoint)
X
Units=ºC
Precision=2
Min=4.4
Max=32.2
Current State
X
Occupied
Unoccupied
Bypass
Standby
Occ Null
Next State
X
Occupied
Unoccupied
Bypass
Standby
Occ Null
Time To Next State
X
Units=min
Precision=0
Min=0.0
Max=65535.0
DLC Shed
X
dlNul
dlNoDlcShed
dlMinDlcShed
Cover Communication Failed
X
False or True
Invalid IO Configuration
X
False or True
Invalid SubBase Type
X
False or True
Network Communication Failed
X
False or True
Sensor Failed
X
False or True
Application Mode
X
X
X
X
Default
Auto
Heat
Morning Warmup
Cool
Night Purge
Pre-cool
Off
Test
Emergency Heat
Fan Only
Free Cool
Ice
Maximum Heat
Economy
Dehumidify
Calibrate
Emergency Cool
Emergency Steam
Max Cool
HVAC Load
No Load
Fan Mode
X
X
X
X
Auto or Continuous
Table 93. T7350 Application of Points. (Continued)
Point Name
Graphics Alarms Trends
Commandable
Internal Use
Valid Values