Choose the number of cooling stages (1-4) or the type
(PWM or Floating) from the Cooling list.
8.
Select the type of economizer from the Economizer list.
a. If the heating, cooling, or economizer is configured
as PWM, the Period, Zero Scale, and Full Scale
settings must be configured.
b. If the heating, the cooling, or the economizer is
configured as Floating, the Motor speed settings
must be configured.
9.
Configure the Optional points. Refer to Table 16 on
page 45 for possible values.
10.
Click
Commit
to save the settings or
Reset
to revert to
the last saved settings.
11.
Click
Next
to display the
Input Configuration
page.
CVAHU Controller Outputs
Table 16 lists the CVAHU Outputs for each controller model.
NOTE: The optional points Free1AO, Free2AO,
Free1AORev, Free2AORev are available in the
W7750C Model of CVAHU only. These enumerations
must be selected to use terminals 6,7 and 8 of
W7750C model. These outputs can be driven by
XL15A or XL15C, but since Free1 and Free2 are
digital in nature, XL15A and XL15C can only
command these points to ON or OFF. Hence, these
points can be driven only by digital outputs of Xl15A/
Xl15C loops.
CVAHU Outputs fields
Table 17 lists the CVAHU Outputs fields.
Table 16. CVAHU Outputs for each Model.
Output
W7750A
W7750B
W7750C
Heating
1 to 4 stages
1 to 4 stages, HeatPWM or
HeatingFloating
1 to 4 stages, HeatPWM,
HeatPWMRev, HeatAO,
HeatAORev, or HeatingFloating.
Cooling
1 to 4 stages
1 to 4 stages, CoolPWM or
CoolingFloating
1 to 4 stages, CoolPWM,
CoolPWMRev, CoolAO,
CoolAORev, or CoolingFloating.
Economizer
EconNone or EconFloating
EconNone, EconPWM, or
EconFloating
EconNone, EconPWM,
EconPWMRev, EconAO,
EconAORev or EconFloating.
Optional Points OccStatus, AuxEcon, Free1, Free2,
Free1PulseOn, Free1PulseOff.
Maximum of one optional point.
OccStatus, AuxEcon, Free1, Free2,
Free1PulseOn, Free1PulseOff.
Maximum of three optional points.
OccStatus, AuxEcon, Free1,
Free1Rev, Free2, Free2Rev
Free1PulseOn, Free1PulseOff,
Free1AO, Free1AORev, Free2AO,
Free2AORev.
No optional points available.
Table 17. CVAHU Outputs Fields.
Name
Definition
Controller Type
Select one of the following model types:
•
W7750A
•
W7750B
•
W7750C
The wizard does not allow commissioning
if incorrect Model Type is selected
Power Frequency Select one of the following options:
•
50 Hz
•
60 Hz
Equipment Type
Select one of the following options:
•
Conventional
•
HeatPump
Heating
Refer to table above for selecting Heating
options:
•
If you select Floating, enter the Motor
Speed settings.
•
If you select PWM, enter the PWM
settings.
Cooling
Refer to the table above for selecting
Cooling settings:
•
If you select Floating, enter the Motor
Speed settings.
•
If you select PWM, enter the PWM
settings.
Economizer
Refer to the table above for selecting
Economizer options:
•
If you select Floating, enter the Motor
Speed settings.
•
If you select PWM, enter the PWM
settings.
Table 17. CVAHU Outputs Fields. (Continued)
Name
Definition