WEBVISION™
95-7769—01
62
FCU Switching Levels
Purpose
To configure fan switching level and staged output switching
levels.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1.
Click the
Switching
Levels button on the left pane to
open the
Switching Levels Configuration
page.
2.
Enter information into available fields.
3.
Click
Commit
to save the settings or
Reset
to revert to
the last saved settings.
4.
Click
Next
to display the
Zone Control Configuration
page or
Back
to display the
Fan Configuration
page.
FCU Switching Levels fields
Acceptable range for all levels is 0% to 100%. A setting of 0%
means the fan is OFF for this and the following stages.
FCU Zone Control
Purpose
Configure the heating and cooling setpoints for the Occupied,
Standby and Unoccupied operating modes.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1.
Click the
Zone Control
button on the left pane to open
the
Zone Control Configuration
page.
2.
Enter information into available fields.
3.
Click
Commit
to save the settings or
Reset
to revert to
the last saved settings.
4.
Click
Next
to display the
Miscellaneous Configuration
page or
Back
to display the
Switching Levels
Configuration
page.
FCU Zone Control fields
Setpoints can range from 10 to 35 °C (50 to 95 °F).
FCU Miscellaneous
Purpose
To configure energy management parameters.
Mode
Configuration can be performed with the wizard Off-line or
On-line.
Procedure
1.
Click the
Miscellaneous
button on the left pane to open
the
Miscellaneous Parameters Configuration
page.
2.
Enter information into available fields.
3.
Click
Commit
to save the settings or
Reset
to revert to
the last saved settings.
4.
Click
Next
to display the
PID Configuration
page or
Back
to display the
Zone Control Configuration
page.
FCU Miscellaneous fields
Table 36. FCU Zone Control Options.
Name
Definitions
Temperature
Setpoints
Cooling/Heating
Occupied
Setpoints during Occupied mode. Setpoints
can range from 10 to 35 °C (50 to 95 °F).
Standby
Setpoints during Standby mode. Setpoints can
range from 10 to 35 °C (50 to 95 °F).
Unoccupied
Setpoints during Unoccupied mode. Setpoints
can range from 10 to 35 °C (50 to 95 °F).
Table 37. FCU Miscellaneous Field Options.
Name
Definitions
Miscellaneous Configures operator bypass and priority
options.
Bypass Time
Define the period of time (0 to 1080 minutes)
in which the controller operates to occupied
setpoints after the local user has pressed the
override button.
Override Priority
Allocate priority between local wall module
operations (for example, Bypass) and
commands from the building management
central. Choices are:
Last Wins
- Last received input takes
precedence. It can be either the Bypass
button or the Network signal.
Network Wins
- The Network signal
always takes precedence over the Bypass
button.
Energy
Management
DLC SetPoint Bump
For load shedding applications. Define the
temporary setpoint shift to be added to the
setpoint when the controller receives a Load
Shedding command. By raising the setpoint
during cooling operation, or reducing the
setpoint during heating operation, the
controller reduces the amount of heat or cool
energy dissipated as a contribution to load
shed algorithms.
•
The parameter can be set in the range 0 to
10 DDC (0 to 18 DDF).
Table 36. FCU Zone Control Options. (Continued)
Name
Definitions