XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
43
Backup-Alarm Switches
Installation
3.9 Backup-Alarm Switches
Backup alarm switches are provided that enable NACs
and the alarm relay to activate during a backup alarm
condition. If the main board’s microcontroller fails and
an alarm is reported by any detector or a monitor
module that has backup reporting enabled, the NAC
will turn on if the corresponding switch was enabled.
The alarm will activate during microcontroller failure
regardless of the settings of Switch 6-9.
•
Switch 6 - NAC#1
•
Switch 7 - NAC#2
•
Switch 8 - NAC#3
•
Switch 9 - NAC#4
So, for example, if Switch 6 and Switch 8 were enabled at the time of an alarm during
microcontroller failure, NAC#1 and NAC#3 would activate. Follow sequence of steps in Section
3.2 “Installation Checklist”, Table 3.1; this is Step 7.
3.10 Installing a Transmitter Module TM-4
TM-4 is power-limited. Connections are on TB7 nonresettable output and TB13 EIA-485 ACS
Mode. Refer to the
Transmitter Module TM-4
installation document for installation details.
3.11 UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25 inches (6.35 mm) from any
nonpower-limited circuit wiring. All power-limited and nonpower-limited circuit wiring must enter
and exit the cabinet through different knockout and or conduits. To maintain separation, group
non-power limited modules together, i.e., group modules on the same side of the enclosure or in
separate rows.
!
WARNING:
Do not enable the BACKUP option switch for any of the four Notification Appliance Circuits (NACs) if
they are used for releasing functions!
ALARM RELAY
NO NC C
TROUBLE RELAY
NO NC C
SUPERVISORY RELAY
NO NC C
SECURITY RELAY
NO NC C
TB8
TB9
TB10
TB
11
SW1
SW5
SUPV ALARM
SECUR ALARM
SW1 is set to Supervisory
SW5 is set to Security
Move switch to opposite
position to set to Alarm.
nfs6
40
-r
el
ay
.cdr
Figure 3.14 Form-C Relay Connections
Figure 3.15 Backup Alarm
Switches
SW
6
NAC
SW7
ENA
B
DISAB
SW
8
SW9
1
3
2
4
nfs6
40
-sw
6-9
.cdr
Summary of Contents for XLS140
Page 8: ...8 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 ...
Page 57: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 57 Notes ...
Page 68: ...68 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 Notes ...
Page 87: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 87 ...