XM500

TCP/IP Modem

GENERAL

The XM500 allows for communication between standard 

EXCEL 5000 controllers and the Excel Building Supervisor 

Central, or any controller on the Light Commercial Building 

System (LCBS) and L

ON

S

TATION

™, via standard Ethernet-

TCP/IP based LAN/WAN networks.

The XM500 is easy to install and to configure. Typically, with 

all necessary network information being available, it can be 

made operational within minutes.

The XM500 converts the serial data received from the 

controller or workstation central into TCP/IP packets and vice 

versa.

On its serial port, the XM500 behaves like a standard Hayes 

compatible modem: It is addressed with Hayes commands, 

and instead of a telephone number, IP addresses are used.

The XM500 is designed to replace the analog modem used in 

our Excel 5000 and LCBS systems and provide the same 

functionality using TCP/IP communications.

The XM500 may be easily configured with the IP Connect 

software provided or manually via Windows Terminal 

Program. The LAN/WAN network server requires no software 

download for the XM500.

FEATURES

• Communication between XBS or L

ON

S

TATION

™ 

centrals and EXCEL 5000 controllers via standard 

Ethernet-TCP/IP LAN/WAN.

• TCP/IP provides more reliable and faster 

communications than analog modem.

• Compatible with all HVAC systems connecting through 

an SLTA-10.

• Compatible to EXCEL 5000 controllers with integrated 

modem communication (O.S. version 2.01.00 or later).

• Compatible to EXCEL 5000 modem devices XM100A, 

XDM506.

• Compatible to all XBS or L

ON

S

TATION

™ centrals with 

dial-up functionality via COM-port.

• Completely self-contained device.
• Quick and easy installation and set-up.

LIMITATIONS

The Echelon MIPS protocol requires all outbound commands/

queries be answered within 1000 milliseconds (1 sec). If any 

part of the Wide Area Network is comprised of a satellite link, 

it is likely to have a “propagation delay” of more than one 

second, thus eliminating the use of a WAN modem. Before 

installation, the user should perform tests to obtain the 

response time of the network. (See “Configuration” on 

page 3.)

Contents

General .............................................................................

1

Features ...........................................................................

1

Limitations ........................................................................

1

Specifications ...................................................................

2

Ordering Information  ........................................................

2

Configuration ....................................................................

3

Programming the XM500  .................................................

4

Technical Installation and Set-Up (Optional)  ....................

6

Summary of Contents for XM500

Page 1: ...ually via Windows Terminal Program The LAN WAN network server requires no software download for the XM500 FEATURES Communication between XBS or LONSTATION centrals and EXCEL 5000 controllers via standard Ethernet TCP IP LAN WAN TCP IP provides more reliable and faster communications than analog modem Compatible with all HVAC systems connecting through an SLTA 10 Compatible to EXCEL 5000 controller...

Page 2: ...emperature 14 to 158 F 10 to 70 C Relative humidity 10 to 95 non condensing Processor and Memory Main processor 68HC000 Ethernet Coprocessor SMC91C96 Memory RAM 64K byte with 2K byte NVRAM EPROM 256K byte Software IP Connect software is provided to configure the XM500 modem The various controllers and workstations are configured using Honeywell specific software for serial communication with EXCEL...

Page 3: ...l serve as the telephone number for the workstation or EXCEL controller that is connected to it EXAMPLE 160 221 71 130 NOTES 1 If communication is only done internally in the LAN unofficial IP addresses will be sufficient 2 If only dynamic IP addresses are available Use a DHCP server and have it allocate the identical IP address every time it does a dynamic IP address allocation 3 For an intermedi...

Page 4: ...blank configuration screen 13 When the modem is ready the status screen should read Please select device XM500 is connecting to 14 Choose the device which the modem is going to be connecting to or the workstation from which the modem is connecting NOTE If you are connecting from XBS make sure you choose the same baud rate as the controller to which you connect 15 Once you have chosen a device the ...

Page 5: ...em is not connected to a network LONSTATION and LONSPEC Configuration 1 Begin from the desktop 2 Double click My Computer 3 Double click Control Panel 4 Double click Modems 5 Click Add 6 Click the box Don t detect my modem I will select it from a list 7 Click Next 8 Under Manufacturers column click Standard Modem Types 9 Under Models column click Standard 28800 bps Modem 10 Click Next IMPORTANT De...

Page 6: ... an IP address 160 221 71 130 with appropriate network mask 255 255 252 0 note the blank space between IP address and network mask d route add net default 160 221 68 1 1 Example of a gateway definition Please check with the local network administrator if a gateway definition is necessary The parameters are the default gateway address 160 221 68 1 and the number of hops to the gateway 1 They must b...

Page 7: ...been initialized it will always and consistently show the same pre defined serial behavior Table 1 Hayes Command Set EXAMPLE Command ping 160 221 71 131 Answer 160 221 71 131 is alive This answer means that the TCP IP communication to the target XM500 is working If the target XM500 cannot be reached the answer will be no answer from 160 221 71 131 Command Description Hang up close connection A A0 ...

Page 8: ...ow control Cable Specifications RS 232 CABLE RJ45 TO DB9 DB25 IMPORTANT The RS 232 cable is a special calibration cable Standard RJ45 to RS 232 connectors will not work Table 3 PIN Assignment RS 232 Cable a Note that the DTR signal is looped back in order to supply DSR to the terminal XBS or EXCEL 5000 CPU ETHERNET CABLE Use a standard 10BASE T twisted pair Ethernet cable with RJ45 plugs LONSPEC a...

Reviews: