background image

ZIO

®

/ZIO PLUS LCD WALL MODULES

19

63-2719—03

OPERATING THE ZIO WALL 

MODULE

There are two modes of operation:

• Contractor mode provides features a contractor would use 

such as selecting the Home screen, selecting parameters 

the tenant can view, and monitoring/modifying controller 

parameters, which includes balancing.

• Tenant mode provides features a tenant would use such as 

changing the setpoint, fan speed or system mode, initiating 

override, or monitoring/modifying permitted controller 

parameters. See page 22 for information about Tenant 

Mode operation.

Contractor Mode (Entering and Exiting)

Contractor mode allows access to the Setup function of the 

wall module.

To enter and exit the Setup function – Press the Up and Down 

arrow keys and the middle softkey all at the same time (see 

Fig. 1 on page 1 for key positions). The TR71/TR75 will 

display the revision and model before going to the next screen 

as shown in Fig. 27.

Fig. 27. On power-up, screen displays revision and Zio model 

number.

If the password option is enabled you will be prompted to 

enter a four digit password as shown in Fig. 28. Use the up/

down arrow keys to change the first number and use the Done 

and Next softkeys to navigate from one digit to the next.

Fig. 28. Password entry screen.

Contractor Mode Operation

Contractor mode allows advanced options (such as modifying 

configured parameters) using the softkeys. Contractor mode 

also allows for customizing the tenant’s view including setting 

the tenant’s Home screen and controlling the tenant’s “View 

More” access, which can provide the tenant with a view of the 

configured parameters.

Contractor Home Screen Softkeys

Fig. 29. Typical Contractor LCD display.

The three softkeys on the contractor Home screen (see Fig. 

29) provide the following:

SET HOME SCREEN allows the contractor to choose among 

multiple Home screen options for the tenant. 

The tenant’s Home screen choices are created by the Con-

figuration Wizard and downloaded to the wall module. Each 

wall module may have different Home screen choices. The 

contractor, using the softkeys, may choose which Home 

screen should be used, and may configure the Tenant view 

to show a subset (or none) of the configured parameters.

• When the contractor clicks the SET HOME 

SCREEN softkey, The display changes as shown in 

Fig. 30, and the softkeys change to DONE, 

CANCEL, and NEXT.

• Clicking the NEXT softkey cycles through the 

configured Home screens (see “Home Screen 

Options” on page 9). 

• Click the DONE softkey when the desired Home 

screen displays. 

• The CANCEL softkey exits the Home screen 

display without saving any changes.

M27357

Summary of Contents for Zio TR70

Page 1: ... three softkeys and two Up Down adjustment keys Models with H also include an onboard humidity sensor PREFACE This Operating Guide is intended to provide configuration information using the Niagara Workbench tool and a general overview of the TR70 Series operator interface Configuration begins with Initial Power Up on page 2 and the general overview begins with Operating the Zio Wall Module on pag...

Page 2: ...Wall Module LCD screen The new Spyder tool 6 0 or greater assumes the latest Spyder capability At download the Tool reads the brand model of the connected Spyder and determines if it matches the features on the wire sheet If old or new Spyder is programmed with aTR70 it can be physically replaced with a TR71 or TR75 Table 1 TR70 Series Features Features Zio TR70 Zio TR71 ZioPlus TR75 Scheduling x ...

Page 3: ...ation and Memory Usage The Honeywell Spyder Tool uses an intuitive window based interface A Help button on each screen provides assistance with any entry or process IMPORTANT Use the Help button to display context specific help for the current window or pane display See the lower left corner of Fig 6 on page 5 for the location of the Help button NOTE At any time clicking the Preview button lower l...

Page 4: ...gories should be below 100 See Fig 4 on page 4 NOTE For a single Zio memory usage must be equal to or less than 100 in order to download the configura tion to the programmable controller If using multiple Zios you should also check the Spyder Resource usage Total Zio memory use is limited to 5K bytes on Spyder View the online help in the WEBs AX Workbench to see troubleshooting tips for reducing m...

Page 5: ...can use the Remove button to delete unused categories and parameters to free up memory space Fig 7 Category Preview CATEGORY DETAILS When you select a category from the Categories tree list and click the Edit button a details pane displays for that category see Fig 8 on page 6 Here you can enter a category name and description The number of parameters in this category are shown The description tex...

Page 6: ...rameter from the tree list and click the Edit button a details pane displays for that parameter Here you can select Viewable by Tenant and Editable by Tenant As an example Fig 10 shows the Details for the ROOMTEMP parameter Here you would enter the description select the parameter type from its drop down list enter the decimal accuracy default sensor offset value temperature units and select the d...

Page 7: ...the data files limits the total number See the memory usage tool by clicking on the Memory Usage Details button in the left pane of the Configuration Wizard The TR71 TR75 may vary from these capacity numbers depending on label names parameter limit reuse and other devices that Zio interacts with on the Sylk bus NOTE Network Variables need to be linked to the appropri ate S Bus wall module s functi...

Page 8: ... related unoccupied heat setpoint parameter as the low limit and the occupied cooling setpoint parameter as the high limit To assign a setpoint to another setpoint s high or low limit click on the Browse button next to the Low Limit or High Limit field From the Select Parameter dialog box you can select the appropriate setpoint This feature is an alternative to assigning a numeric value in the Hig...

Page 9: ...ome screen to be the initial Home screen for the wall module after the configuration is downloaded to the wall module The Description text you enter allows more information to be entered on the home screen and will be loaded to the controller but cannot be previewed Use the Option Type selection to choose either single or multiple 1 to 3 parameters to display on the Home screen For the Single Para...

Page 10: ... Settings button for the Valid States That You Can Override section opens the Override to Occupied Settings dialog box where you can configure values to any desired number from 0 to 255 To conserve Zio memory choose the same Override Type and Timed Override Details for Occupied Unoccupied and Standby Fig 17 Occupancy and Override screens OCCUPANCY STATUS DISPLAY OPTIONS Here you select how the ove...

Page 11: ...ils will be determined by the programmable controller configuration This option only applies to Occupancy override settings Unoccupied and Standby do not use bypass ADVANCED SETTINGS When the Show Advanced Settings button is clicked overrides to Occupied Unoccupied and Standby options are possible The Override to Unoccupied selection s Settings button displays pop ups similar to the Override to Oc...

Page 12: ...the fan commend is a network setpoint then the default value is set on the controller s network setpoint The Fan command value cannot be changed from Zio in the Contractor mode After you choose the setting use the Fan Command Preview at the bottom of the window to exercise the Fan softkey to cycle through the options If the Set as Network Setpoint box is checked for the TR71 TR75 the Preview scree...

Page 13: ...the top of the wall module s LCD screen For TR71 TR75s click on the System Command checkbox to allow the System Command to be configured as a network setpoint The default System Command option is Off Heat Heat Only The System commands are selectable The System command value cannot be changed from Zio in the Contractor mode After you choose the setting use the Preview button at the bottom of the wi...

Page 14: ... or not the tenant can view or edit etc We recommend setting the time in Spyder before configuring the Schedule Time in the configuration tool NOTE Setting an invalid time at Zio will cause Spyder to set the time to invalid You also have the ability to configure how the Spyder schedule will display at the TR75 8 day schedule 7 day schedule 5 2 1 day schedule or the 5 2 schedule If using the 5 2 1 ...

Page 15: ...tem changes from the TR71 TR75 The password option is not available for the TR70 The password can be assigned an eight character label that is displayed at the TR71 TR75 and a four digit password from 0000 to 9999 All TR71 TR75s on a Spyder can have the same or unique passwords If the password option is enabled and the password is forgotten it can be retrieved through the WEBs AX Workbench in the ...

Page 16: ...ey rectangles below the labels of the preview display exercises the features you have configured NOTE Since the up and down arrow keys do not display in Preview mode no adjustments to parameters e g setpoint temperature can be made Fig 24 shows your current configuration of the wall module Home screen You can select either the Tenant or Contractor view The three softkeys in the preview LCD display...

Page 17: ...o see how the wall module LCD screen will operate for your selected configuration see Preview on page 16 Confirm Memory Usage is within Limits To view the current memory use information click on the Memory Usage Details button A new window opens and displays a a bar graph indicating the percentage of current memory used in each memory category Each of the memory categories should be below 100 You ...

Page 18: ...see an example in Fig 26 A maximum of four Zios may be wired on a single Sylk bus with no more than one TR70 per bus When making links from existing blocks to the wall module function block input slots there is no need to break the existing links from these existing blocks The new tool allows for multiple output connections When connecting to slots on function blocks which lie on different wire sh...

Page 19: ...gate from one digit to the next Fig 28 Password entry screen Contractor Mode Operation Contractor mode allows advanced options such as modifying configured parameters using the softkeys Contractor mode also allows for customizing the tenant s view including setting the tenant s Home screen and controlling the tenant s View More access which can provide the tenant with a view of the configured para...

Page 20: ...ey moves to the next parameter Click the DONE softkey when finished The CANCEL softkey exits VIEW MORE without saving changes to that parameter Fig 31 Set View More parameter display PARAMETERS allows the contractor to monitor and or adjust parameters in the programmable controller Clicking the PARAMETERS softkey displays the first configured category as shown in Fig 31 and the softkeys change to ...

Page 21: ... Schedule option lets you modify the schedule and change Spyder s time The desired scheduling option 8 day 7 day etc is setup in the Configuration Wizard see Wall Module Configuration on page 4 and based on that selection option screens vary The example below shows the flow for viewing editing a schedule Use the Edit softkey to move to the next screen and use the up down arrows to change values Wh...

Page 22: ... softkey does not display on the tenant s Home screen 3 If there are no parameters configured for tenant access the VIEW MORE softkey does not display on the tenant s Home screen FAN allows the tenant to adjust the fan settings depending on the fan options 2 3 or 5 position configured As shown in Fig 41 each click of the FAN softkey changes the fan icon display between 2 position ON and AUTO 3 pos...

Page 23: ...finished Fig 43 System and View More display for Tenant Tenant Home Screen Display The LCD display may be customized for the tenant This section includes a few examples of the various tenant Home screens that are configurable for the LCD Wall Modules Not all possible Home screens are illustrated here There are many other configurable Home screens NOTE Home screens can display one to three of any o...

Page 24: ... Home screen with Room Temperature and Time predominant NOTE In Fig 47 there are no Fan System or View More softkey options configured for this Home screen Fig 48 Sample Tenant Home screen with a single custom parameter NOTE In Fig 48 the Home screen is configured with only a single custom parameter See Preview on page 9 Fig 49 View More display showing CO2 sensor value from controller NOTE As sho...

Reviews: