5 FUNCTION
116
5.13.8 Setting the UNIT HIGH ALARM
1.
For each item that you want to set, press the button of the item on its MEAS.
SETTING screen.
Item that you want to set on the MEAS. SETTING screen:
TURB., COL., CL., PRES., pH, COND., TEMP.
The MEAS. SETTING screen of each measurement item is displayed.
2.
Press the UNIT HIGH ALARM button.
The UNIT HIGH ALARM screen is displayed for the appropriate measurement item.
*This example is for the UNIT HIGH ALARM SETTING screen of TURB.
3.
Enter the value using the numerical key pad and press [SET].
Tip
[CLEAR]: Clears the whole value.
[BACK]: Deletes the rightmost number of the value.
The screen returns to the MEAS. SETTING screen for each measurement item.
Displaying the setting screens for each measurement item" (page 92).
MEAS. screen
MAINTENANCE screen
[I/O]
[MAINTE.]
[SETTING]
MEAS.SETTING screen
[(Measurement item)]
MEAS.SETTING screen
UNIT HIGH ALARM
[x.xx FTU]
Measurement item
Input range (same for each setting value)
Default value
Turbidity
1.00 to 5.00 (FTU)
5.00 (FTU)
Color
5.0 to 30.0 (CU)
30.0 (CU)
Residual chlorine
1.00 to 3.00 (mg/L)
3.00 (mg/L)
Water pressure
0.250 to 1.500 (MPa)
1.500 (MPa)
pH (optional)
0.00 to 14.00
14.00
Conductivity (Optional)
10.0 to 75.0 (mS/m)
75.0 (mS/m)
Water temperature (optional)
10.0 to 100.0 (
C)
100.0 (
C)